C2P5 Contamination
Part C2 Sanitary drainage systems · NCC 2019: CP2.1
(1) A sanitary drainage system must ensure protection against internal contamination.
(2) A sanitary drainage system must avoid the entry of water, foul air and gases from the system into buildings.
(3) A sanitary drainage system must avoid the entry of surface water, sub-surface water and stormwater into the system.
Changed in NCC 2025. See NCC 2025 Volume Three C2P5, or show what changed.
(1) A The entry of water, foul gases, sewerage and sullage from a sanitary drainage system into buildings must ensure protection against internal contamination. be avoided. (2) A sanitary drainage system must avoid the be protected against internal contamination. (3) The entry of water, foul air and gases from the system into buildings. (3) A a sanitary drainage system into buildings must avoid the be avoided, such that — at pressures of up to ±375 Pa, water trap seals will not be reduced to depths less than — 70 mm for trap seals in pressurised rooms; and 25 mm for all other applications; or an equivalent level of safety to human health is achieved as a system complying to (a). (4) The entry of surface water, sub-surface water and stormwater into the system. a sanitary drainage system must be avoided.
Removed words are struck through; added words are highlighted. Comparison of the text only.