Delete clause B6D4 and insert NSW B6D4 as follows:

(1) Cisterns or flushing devices for water closets must—

Have a dual flushing mechanism; and

Be a minimum 3 Star WELS rating discharging not more than 6 litres or 4.5 litre for a full flush.

(2) Cisterns or flushing devices for urinals must—

Be a minimum 2 Star WELS rating discharging a volume of not more than 2.5 litres of each—

Single urinal stall; or

600mm length of continuous urinal wall; and

Not be set-cycled or activated by any method other than manual or use activation.

Applications

The flush volumes of B3D5(2) and B3D5(3) may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of B6D4 do not apply to a vacuum drainage system.

The requirements of B6D4(2)(c) not apply to a programmed solenoid operated flushing system if programmed to shut down during extended periods of non-occupancy of a building.