Deemed-to-Satisfy Provision · NCC 2025 Volume Three

B3D5 Water efficiency

Part B3 Non-drinking water services

Open B3D5 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) Cisterns or flushing devices for water closets must—

have a dual flushing mechanism; and

be a minimum 3 Star WELS rating, discharging not more than 6 litres or 4.5 litres for a full flush.

(2) Cisterns or flushing devices for urinals must—

be a minimum 2 Star WELS rating, discharging a volume of not more than 2.5 litres for each—

single urinal stall; or

600mm length of continuous urinal wall; and

not be set-cycled or activated by any method other than manual or use activation.

Applications

The flush volumes of B3D5(2) and B3D5(3) may be within a tolerance of—

±0.5 litres for the full flush of a 6/3 litre cistern; or

+0.5 litres for the reduced flush of a 6/3 litre cistern; or

±0.2 litres for a 4.5/3 litre cistern.

Exemptions

The requirements of B3D5(2) and B3D5(3) do not apply to a vacuum drainage system.

The requirements of B3D5(3)(b) do not apply to a programmed solenoid operated flushing system if programmed to shut down during extended periods of non-occupancy of a building.

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three B3D5.
Can't meet B3D5? A Performance Solution must meet the Performance Requirements it satisfies: B3P1, B3P2, B3P3, B3P4, B3P5, B3P6, B3P7, B3P8. Start a Performance Solution →

State and territory variations all clauses side by side →

Defined terms used