Tasmania variation · NCC 2025 Volume Three

TAS B2D6 Temperature control devices

TAS Part B2 Heated water services · varies B2D6 Temperature control devices

Open on NCC Online ↗

Delete clause B2D6 and insert TAS B2D6 as follows:

(1) A temperature control device used to deliver heated water in accordance with B2D5(a) must be a—

thermostatic mixing valve; or

thermostatically controlled tap.

(2) A temperature control device used to deliver heated water in accordance with B2D5(b) must be a—

thermostatic mixing valve; or

thermostatically controlled tap; or

tempering valve; or

temperature limited water heater limited to 50°C in accordance with AS 3498.

(3) The required maximum delivery temperature must be achieved in accordance with AS/NZS 3500.4.

Applications

B2D6 only applies to new and replacement heated water installations.

Exemptions

B2D6 does not apply to the replacement of a single heated water storage unit within a range or bank of heaters.

Same wording in NCC 2022 Volume Three. See NCC 2022 Volume Three TAS B2D6.