TAS B2D6 Temperature control devices
Part B2 Heated water services · varies B2D6 Temperature control devices
Delete clause B2D6 and insert TAS B2D6 as follows:
(1) A temperature control device used to deliver heated water in accordance with B2D5(a) must be a—
thermostatic mixing valve; or
thermostatically controlled tap.
(2) A temperature control device used to deliver heated water in accordance with B2D5(b) must be a—
thermostatic mixing valve; or
thermostatically controlled tap; or
tempering valve; or
temperature limited water heater limited to 50°C in accordance with AS 3498.
(3) The required maximum delivery temperature must be achieved in accordance with AS/NZS 3500.4.
Applications
B2D6 only applies to new and replacement heated water installations.
Exemptions
B2D6 does not apply to the replacement of a single heated water storage unit within a range or bank of heaters.