Verification Method · NCC 2025 Volume Two

H2V1 Weatherproofing

Part H2 Damp and weatherproofing · NCC 2019: V2.2.1

Open H2V1 on NCC Online ↗

(1) Compliance with H2P2 for weatherproofing of an external wall is verified when—

a prototype passes the procedure described in (2); and

the external wall —

has a risk score of 20 or less, when the sum of all risk factor scores are determined in accordance with Table H2V1a; and

includes only windows that comply with AS 2047.

(2) The test procedure referred to in (1)(a) must be as follows:

The test specimen is in accordance with the requirements of (3).

The test procedure is in accordance with the requirements of (4) and (5) as appropriate.

The test specimen does not fail the criteria in (6).

The test is recorded in accordance with the requirements of (7).

(3) Test specimen: The test specimen must be a minimum of 2.4 m high and 2.4 m wide and incorporate—

representative samples of openings and joints, including—

vertical and horizontal control joints; and

wall junctions; and

windows or doors; and

electrical boxes; and

balcony drainage and parapet flashings; and

footer and header termination systems; and

for a cavity wall —

a transparent material for a proportion of the internal wall lining (to provide an unobstructed view of the external wall cladding) with sufficient structural capability and similar air tightness to resist the applied wind pressures; and

a 15 mm diameter hole in the internal wall lining below a window.

(4) The test procedure for a direct fix cladding wall or unique wall must be as follows:

Apply 100% positive and negative serviceability wind pressures to the external face of the test specimen for a period of not less than 1 minute each.

Apply static pressure of either 300 Pa or 30% serviceability wind pressure, whichever is higher, in accordance with the water penetration test procedure at clause 8.5.2 of AS/NZS 4284.

Apply cyclic pressure in accordance with—

the three stages of Table H2V1b; and

the water penetration test procedure at clause 8.6.2 of AS/NZS 4284.

(5) The test procedure for a cavity wall must be as follows:

Apply 100% positive and negative serviceability wind pressures to the external face of the test specimen for a period of not less than 1 minute each.

Apply static pressure of either 300 Pa or 30% serviceability wind pressure, whichever is higher, in accordance with the water penetration test procedure at clause 8.5.2 of AS/NZS 4284.

Apply cyclic pressure in accordance with—

stage 3 of Table H2V1b; and

the water penetration test procedure at clause 8.6.2 of AS/NZS 4284.

To simulate the failure of the primary weather-defence or sealing, the following procedure must be applied to the test specimen:

Insert 6 mm diameter holes through the external face of the cavity wall in all places specified below:

Wall/window or wall/door junctions at ¾ height.

Immediately above the head flashing.

Through external sealing of the horizontal and vertical joints.

Above any other penetration detail not covered by (A) to (C).

Repeat the static and cyclic pressure tests of (b) and (c).

Within 30 minutes of the completion of (ii), remove the internal lining of the cavity wall and check for compliance with (6).

With the internal lining removed, apply a final static pressure test at 50 Pa for a period of 15 minutes and check for compliance with (6).

(6) Compliance:

A direct fix cladding wall and unique wall are verified for compliance with H2P2 if there is no presence of water on the inside surface of the facade.

A cavity wall is verified for compliance with H2P2 if there is no presence of water on the removed surface of the cavity, except that during the simulation of the failure of the primary weather-defence or sealing, water may—

transfer to the removed surface of the cavity due to the introduced defects (6 mm holes); and

contact, but not pool on, battens and other cavity surfaces.

(7) Test report — The test report must include the following information:

Name and address of the person supervising the test.

Test report number.

Date of the test.

Cladding manufacturer’s name and address.

Construction details of the test specimen, including a description, and drawings and details of the components, showing modifications, if any.

Test sequence with the pressures used in all tests.

For each of the static and cyclic pressure tests, full details of all leakages, including position, extent and timing.

Table H2V1a Risk factors and scores

Risk factor

Category

Risk severity

Score

Wind region

Region A(0-5) (AS/NZS 1170.2)

Low to medium

0

Region B1-2 (AS/NZS 1170.2)

Low to medium

0

Region C (AS/NZS 1170.2)

High

1

Region D (AS/NZS 1170.2)

Very high

2

Number of storeys

One storey

Low

0

Two storeys in part

Medium

1

Two storeys

High

2

More than two storeys

Very high

4

Roof/wall junctions

Roof-to-wall junctions fully protected

Low

0

Roof-to-wall junctions partially exposed

Medium

1

Roof-to-wall junctions fully exposed

High

3

Roof elements finishing within the boundaries formed by the external walls

Very high

5

Eaves width

Greater than 600 mm for single storey

Low

0

451-600 mm for single storey

Medium

1

Greater than 600 mm for two storey

Medium

1

101-450 mm for single storey

High

2

451-600 mm for two storey

High

2

Greater than 600 mm for above two storey

High

2

0-100 mm for single storey

Very high

5

0-450 mm for two storey

Very high

5

Less than 600 mm for above two storey

Very high

5

Envelope complexity

Simple shape with single cladding type

Low

0

Complex shape with no more than two cladding types

Medium

1

Complex shape with more than two cladding types

High

3

As for high risk but with fully exposed roof-to-wall junctions

Very high

6

Decks, porches and balconies

None

Low

0

Timber slat deck or porch at ground level

Low

0

Fully covered in plan view by roof

Medium

2

Timber slat deck attached at first or second floor level

Medium

2

Balcony exposed in plan view at first floor level

High

4

Balcony cantilevered at first floor level

High

4

Balcony exposed in plan view at second floor level or above

Very high

6

Balcony cantilevered at second floor level or above

Very high

6

Table Notes

Eaves width is measured horizontally from the external face of any wall cladding to the outer edge of any overhang, including fascia and external gutters.

Barriers to prevent falling and parapets are considered as 0 mm eaves.

Table H2V1b Serviceability wind pressure

Stage number

Serviceability wind pressure

1

15% to 30%

2

20% to 40%

3

30% to 60%

Tables

Changed since NCC 2022. See NCC 2022 Volume Two H2V1, or show what changed.

(1) Compliance with H2P2 for weatherproofing of an external wall … risk factor scores are determined in accordance with Table H2V1a; and is not subjected to an ultimate limit state wind pressure of more than 2.5 kPa; and includes only windows that comply with AS 2047. (2) … requirements of (7). (3) Test specimen: The test specimen must be a minimum of 2.4 m high and 2.4 m wide and incorporate — representative samples of openings and joints, including — … pressure test at 50 Pa for a period of 15 minutes. minutes and check for compliance with (6). (6) Compliance: A direct fix cladding wall and unique wall … to 30% 2 20% to 40% 3 30% to 60%

Removed words are struck through; added words are highlighted. Comparison of the text only.

Clauses referred to