Table H4V3 Maximum contaminant limits for acceptable indoor air quality

Part H4 Health and amenity

Open Table H4V3 on NCC Online ↗
PollutantAveraging TimeMaximum Air Quality Value
Carbon dioxide, CO28 hours850 ppm Note 1
Carbon monoxide, CO15 minutes90 ppm
Carbon monoxide, CO30 minutes50 ppm
Carbon monoxide, CO1 hour25 ppm
Carbon monoxide, CO8 hours10 ppm
Formaldehyde, CH2O30 minutes0.1 mg/m3
Nitrogen dioxide, NO21 year40 μg/m3 (0.0197 ppm) Note 2
Nitrogen dioxide, NO21 hour200 μg/m3 (0.0987 ppm) Note 2
Ozone, O38 hour, daily maximum100 μg/m3 (0.0473 ppm)
Particulate matter, PM2.51 year10 μg/m3
Particulate matter, PM2.524 hour (99th percentile)25 μg/m3
Particulate matter, PM101 year20 μg/m3
Particulate matter, PM1024 hour (99th percentile)50 μg/m3
Total volatile organic compounds1 hour500 μg/m3

Table Notes

Based on body odour metric (i.e. 450 ppm above ambient CO2 level of 400 ppm and demand control ventilation provisions in AS 1668.2).

Based on pressure of 101.325 kPa and temperature of 25 degrees (i.e. the conversion is mg/m3 = ppm (molecular weight/24.4)).