Deemed-to-Satisfy Provision · NCC 2025 Volume One
C2D6 Two storey Class 2, 3 or 9c buildings
Part C2 Fire resistance and stability · NCC 2019: C1.5
A building having a rise in storeys of 2 may be of Type C construction if—
it is a Class 2 or 3 building or a mixture of these classes and each sole-occupancy unit has—
access to at least 2 exits; or
its own direct access to a road or open space; or
it is a Class 9c building protected throughout with a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and complies with the maximum compartment size specified in Table C3D3 for Type C construction.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C2D6.
Can't meet C2D6? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →