Deemed-to-Satisfy Provision · NCC 2025 Volume One

C2D10 Non-combustible building elements

Part C2 Fire resistance and stability · NCC 2019: C1.9

Open C2D10 on NCC Online ↗

(1) In a building required to be of Type A or B construction, the following building elements and their components must be non-combustible:

External walls and common walls, including all components incorporated in them including the facade covering, framing and insulation.

The flooring and floor framing of lift pits.

Non-load bearing internal walls where they are required to be fire-resisting.

(2) A shaft, being a lift, ventilating, pipe, garbage, or similar shaft that is not for the discharge of hot products of combustion, that is non-load bearing, must be of non-combustible construction in—

a building required to be of Type A construction; and

a building required to be of Type B construction, subject to C3D11, in—

a Class 2, 3 or 9 building; and

a Class 5, 6, 7 or 8 building if the shaft connects more than 2 storeys.

(3) A load bearing internal wall and a load bearing fire wall, including those that are part of a load bearing shaft, must comply with Specification 5.

(4) The requirements of (1) and (2) do not apply to the following:

Gaskets.

Caulking.

Sealants.

Termite management systems.

Glass, including laminated glass, and associated adhesives, including tapes.

Thermal breaks associated with—

glazing systems; or

external wall systems, where the thermal breaks—

are no larger than necessary to achieve thermal objectives; and

do not extend beyond one storey; and

do not extend beyond one fire compartment.

Damp-proof courses.

Compressible fillers and backing materials, including those associated with articulation joints, closing gaps not wider than 50 mm.

Isolated—

construction packers and shims; or

blocking for fixing fixtures; or

fixings, including fixing accessories; or

acoustic mounts.

Waterproofing materials applied to the external face, used below ground level and up to 250 mm above ground level.

Joint trims and joint reinforcing tape and mesh of a width not greater than 50 mm.

Weather sealing materials, applied to gaps not wider than 50 mm, used within and between concrete elements.

Wall ties and other masonry components complying with AS/NZS 2699 Part 1 and Part 3 as appropriate, and associated with masonry wall construction.

Reinforcing bars and associated minor elements that are wholly or predominately encased in concrete or grout.

A paint, lacquer or a similar finish or coating.

Adhesives, including tapes, associated with stiffeners for cladding systems.

Fire-protective materials and components required for the protection of penetrations.

(5) The following materials, when entirely composed of itself, are non-combustible and may be used wherever a non-combustible material is required:

Concrete.

Steel, including metallic coated steel.

Masonry, including mortar.

Aluminium, including aluminium alloy.

Autoclaved aerated concrete, including mortar.

Iron.

Terracotta.

Porcelain.

Ceramic.

Natural stone.

Copper.

Zinc.

Lead.

Bronze.

Brass.

(6) The following materials may be used wherever a non-combustible material is required:

Plasterboard.

Perforated gypsum lath with a normal paper finish.

Fibrous-plaster sheet.

Fibre-reinforced cement sheeting.

Pre-finished metal sheeting having a combustible surface finish not exceeding 1 mm thickness and where the Spread-of-Flame Index of the product is not greater than 0.

Sarking-type materials that do not exceed 1 mm in thickness and have a Flammability Index not greater than 5.

Bonded laminated materials where—

each lamina, including any core, is non-combustible; and

each adhesive layer does not exceed 1 mm in thickness and the total thickness of the adhesive layers does not exceed 2 mm; and

the Spread-of-Flame Index and the Smoke-Developed Index of the bonded laminated material as a whole do not exceed 0 and 3 respectively; and

when located externally, are fixed in accordance with C2D15.

Changed since NCC 2022. See NCC 2022 Volume One C2D10, or show what changed.

(1) In a building required to be of Type A … and insulation. The flooring and floor framing of lift pits. Non-loadbearing Non-load bearing internal walls where they are required to be fire-resisting. (2) … for the discharge of hot products of combustion, that is non-loadbearing, non-load bearing, must be of non-combustible construction in — a building required … if the shaft connects more than 2 storeys. (3) A loadbearing load bearing internal wall and a loadbearing load bearing fire wall, including those that are part of a loadbearing load bearing shaft, must comply with Specification 5. (4) The requirements of … concrete elements. Wall ties and other masonry components complying with AS AS/NZS 2699 Part 1 and Part 3 as appropriate, and associated … and when located externally, are fixed in accordance with C2D15.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet C2D10? A Performance Solution must meet the Performance Requirements it satisfies: C1P1, C1P2, C1P3, C1P4, C1P5, C1P6, C1P7, C1P8, C1P9. Start a Performance Solution →