C4D16 Construction joints
Part C4 Protection of openings · NCC 2019: C3.16
(1) Construction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation must be protected in a manner—
identical with a prototype tested in accordance with AS 4072.1 and AS 1530.4 to achieve the required FRL; or
that differs from a prototype in accordance with Section 4 of AS 4072.1 and achieves the required FRL.
(2) The determination of the required FRL must be confirmed in a report from an Accredited Testing Laboratory in accordance with Specifications 1 and 2.
(3) The requirements of (1) do not apply where joints, spaces and the like between fire-protected timber elements are provided with cavity barriers in accordance with Specification 9.