Deemed-to-Satisfy Provision · NCC 2025 Volume One

C4D16 Construction joints

Part C4 Protection of openings · NCC 2019: C3.16

Open C4D16 on NCC Online ↗

(1) Construction joints, spaces and the like in and between building elements required to be fire-resisting with respect to integrity and insulation must be protected in a manner—

identical with a prototype tested in accordance with AS 4072.1 and AS 1530.4 to achieve the required FRL; or

that differs from a prototype in accordance with Section 4 of AS 4072.1 and achieves the required FRL.

(2) The determination of the required FRL must be confirmed in a report from an Accredited Testing Laboratory in accordance with Specifications 1 and 2.

(3) The requirements of (1) do not apply where joints, spaces and the like between fire-protected timber elements are provided with cavity barriers in accordance with Specification 9.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One C4D16.