D3D12 Fire-isolated passageways
Part D3 Construction of exits · NCC 2019: D2.11
(1) The enclosing construction of a fire-isolated passageway must have an FRL when tested for a fire outside the passageway in another part of the building of—
if the passageway discharges from a fire-isolated stairway or ramp — not less than that required for the stairway or ramp shaft; or
in any other case — not less than 60/60/60.
(2) Notwithstanding (1)(b), the top construction of a fire-isolated passageway need not have an FRL if the walls of the fire-isolated passageway extend to the underside of—
a non-combustible roof covering; or
a ceiling having a resistance to the incipient spread of fire of not less than 60 minutes separating the roof space or ceiling space in all areas surrounding the passageway within the fire compartment.