D3D11 Pedestrian ramps
Part D3 Construction of exits · NCC 2019: D2.10
(1) A fire-isolated ramp may be substituted for a fire-isolated stairway if the construction enclosing the ramp and the width and ceiling height comply with the requirements for a fire-isolated stairway.
(2) A ramp serving as a required exit must—
where the ramp is also serving as an accessible ramp under Part D4, be in accordance with AS 1428.1; or
in any other case, have a gradient not steeper than 1:8.
(3) The floor surface of a ramp, other than a threshold ramp, must have a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586.