D3D14 Goings and risers
Part D3 Construction of exits · NCC 2019: D2.13
(1) A stairway must have—
not more than 18 and not less than 2 risers in each flight; and
going (G), riser (R) and quantity (2R + G) in accordance with Table D3D14, except as permitted by (2) and (3); and
constant goings and risers throughout each flight, except as permitted by (2) and (3), and the dimensions of goings (G) and risers (R) in accordance with (1)(b) are considered constant if the variation between—
adjacent risers, or between adjacent goings, is no greater than 5 mm; and
the largest and smallest riser within a flight, or the largest and smallest going within a flight, does not exceed 10 mm; and
risers which do not have any openings that would allow a 125 mm sphere to pass through between the treads; and
treads which have—
a surface with a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586; or
a nosing strip with a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586; and
treads of solid construction (not mesh or other perforated material) if the stairway is more than 10 m high or connects more than 3 storeys; and
in a Class 9b building, not more than 36 risers in consecutive flights without a change in direction of at least 30°; and
in the case of a required stairway, no winders in lieu of a landing.
(2) In the case of a non-required stairway—
the stairway must have—
not more than 3 winders in lieu of a quarter landing; and
not more than 6 winders in lieu of a half landing; and
the going of all straight treads must be constant throughout the same flight and the dimensions of goings (G) is considered constant if the variation between—
adjacent goings, is no greater than 5 mm; and
the largest and smallest going within a flight, does not exceed 10 mm; and
the going of all winders in lieu of a quarter or half landing may vary from the going of the straight treads within the same flight provided that the going of all such winders is constant.
(3) Where a stairway discharges to a sloping public walkway or public road—
the riser (R) may be reduced to account for the slope of the walkway or road; and
the quantity (2R+G) may vary at that location.
Table D3D14 Riser and going dimensions
Stairway location
Riser (R)
Going (G)Note 3
Quantity (2R + G)
Max
Min
Max
Min
Max
Min
Public
190
115
355
250
700
550
Private Note 1
190
115
355
240
700
550
Table Notes
Private stairways are—
stairways in a sole-occupancy unit in a Class 2 building or Class 4 part of a building; and
in any building, stairways which are not part of a required exit and to which the public do not normally have access.
Going and riser dimensions must be measured in accordance with Figure D3D14.
The going in tapered treads (except winders in lieu of a quarter or half landing) in a curved or spiral stairway is measured—
270 mm in from the outer side of the unobstructed width of the stairway if the stairway is less than 1 m wide (applicable to a non-required stairway only); and
270 mm from each side of the unobstructed width of the stairway if the stairway is 1 m wide or more.
Figure D3D14 Riser and going dimensions