D3D15 Landings
Part D3 Construction of exits · NCC 2019: D2.14
In a stairway—
landings having a maximum gradient of 1:50 may be used in any building to limit the number of risers in each flight and each landing must—
be not less than 750 mm long, and where this involves a change in direction, the length is measured 500 mm from the inside edge of the landing; and
have—
a surface with a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586; or
a strip at the edge of the landing with a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586, where the edge leads to a flight below; and
in a Class 9a building—
the area of any landing must be sufficient to move a stretcher, 2 m long and 600 mm wide, at a gradient not more than the gradient of the stairs, with at least one end of the stretcher on the landing while changing direction between flights; or
the stair must have a change of direction of 180°, and the landing a clear width of not less than 1.6 m and a clear length of not less than 2.7 m.
Table D3D15 Slip-resistance classification
Application
Dry surface conditions
Wet surface conditions
Ramp steeper than 1:14
P4 or R11
P5 or R12
Ramp steeper than 1:20 but not steeper than 1:14
P3 or R10
P4 or R11
Tread or landing surface
P3 or R10
P4 or R11
Nosing or landing edge strip
P3
P4