Deemed-to-Satisfy Provision · NCC 2022 Volume One

D3D15 Landings

Part D3 Construction of exits · NCC 2019: D2.14

Open D3D15 on NCC Online ↗

In a stairway—

landings having a maximum gradient of 1:50 may be used in any building to limit the number of risers in each flight and each landing must—

be not less than 750 mm long, and where this involves a change in direction, the length is measured 500 mm from the inside edge of the landing; and

have—

a surface with a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586; or

a strip at the edge of the landing with a slip-resistance classification not less than that listed in Table D3D15 when tested in accordance with AS 4586, where the edge leads to a flight below; and

in a Class 9a building—

the area of any landing must be sufficient to move a stretcher, 2 m long and 600 mm wide, at a gradient not more than the gradient of the stairs, with at least one end of the stretcher on the landing while changing direction between flights; or

the stair must have a change of direction of 180°, and the landing a clear width of not less than 1.6 m and a clear length of not less than 2.7 m.

Table D3D15 Slip-resistance classification

Application

Dry surface conditions

Wet surface conditions

Ramp steeper than 1:14

P4 or R11

P5 or R12

Ramp steeper than 1:20 but not steeper than 1:14

P3 or R10

P4 or R11

Tread or landing surface

P3 or R10

P4 or R11

Nosing or landing edge strip

P3

P4

Tables

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One D3D15.
Can't meet D3D15? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P9. Start a Performance Solution →