D3D19 Openings in barriers
Part D3 Construction of exits · NCC 2019: Table D2.16a
(1) Except where allowed by (2), openings in a required barrier must not allow a 125 mm sphere to pass through.
(2) In a fire-isolated stairway, fire-isolated ramp or other area used primarily for emergency purposes, openings in a required barrier—
must not allow a 300 mm sphere to pass through; or
where rails are used—
a 150 mm sphere must not be able to pass through the opening between the nosing line of the stair treads and the rail or between the rail and the floor of the landing, balcony or the like; and
the opening between rails must not be more than 460 mm.
(3) In Class 7 (other than carparks) and Class 8 buildings, openings in a required barrier—
must not allow a 300 mm sphere to pass through; or
where rails are used—
a 150 mm sphere must not be able to pass through the opening between the nosing line of the stair treads and the rail or between the rail and the floor of the landing, balcony or the like; and
the opening between the rails must not be more than 460 mm.
(4) The requirements of (2) do not apply to external stairways, external ramps, or fire-isolated stairways or fire-isolated ramps serving Class 9b early childhood centres.
(5) For a barrier provided under (1), the maximum 125 mm barrier opening for a stairway, such as a non fire-isolated stairway, is measured above the nosing line of the stair treads.
(6) Where a required barrier is fixed to the vertical face forming an edge of a landing, balcony, deck, stairway or the like, the opening formed between the barrier and the face must not exceed 40 mm.
(7) For the purposes of (6), the opening is measured horizontally from the edge of the trafficable surface to the nearest internal face of the barrier.