Deemed-to-Satisfy Provision · NCC 2025 Volume One
D3D20 Barrier climbability
Part D3 Construction of exits · NCC 2019: Table D2.16a
(1) A barrier required by D3D17, located on a floor more than 4 m above the surface beneath, must not incorporate horizontal or near horizontal elements that could facilitate climbing between 150 mm and 760 mm above the floor.
(2) The requirements of (1) do not apply to—
fire-isolated stairways, fire-isolated ramps and other areas used primarily for emergency purposes, other than—
external stairways; and
external ramps; and
Class 7 (other than carparks) and Class 8 buildings.
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One D3D20.