D3D17 Barriers to prevent falls
Part D3 Construction of exits · NCC 2019: D2.16(a), (b) and (c)
(1) A continuous barrier must be provided along the side of—
a roof to which general access is provided; and
a stairway or ramp; and
a floor, corridor, hallway, balcony, deck, verandah, mezzanine, access bridge or the like; and
any delineated path of access to a building,
if the trafficable surface is 1 m or more above the surface beneath.
(2) The requirements of (1) do not apply to—
the perimeter of a stage, rigging loft, loading dock or the like; or
areas referred to in D3D23; or
a retaining wall, unless the retaining wall forms part of, or is directly associated with, a delineated path of access to a building from the road, or a delineated path of access between buildings; or
a barrier provided to an openable window covered by D3D29.
(3) A barrier required by (1) must be constructed in accordance with D3D18, D3D19, D3D20 and, if a wire barrier is used, D3D21.
Changed since NCC 2022 (minor wording). See NCC 2022 Volume One D3D17, or show what changed.
(1) A continuous barrier must be provided along the side … the retaining wall forms part of, or is directly associated with with, a delineated path of access to a building from the … D3D19, D3D20 and, if a wire barrier is used, D3D21.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Clauses referred to
- D3D23 Fixed platforms, walkways, stairways and ladders
- D3D29 Protection of openable windows
- D3D18 Height of barriers
- D3D19 Openings in barriers
- D3D20 Barrier climbability
- D3D21 Wire barriers