Deemed-to-Satisfy Provision · NCC 2025 Volume One

D3D28 Signs on doors

Part D3 Construction of exits · NCC 2019: D2.23

Open D3D28 on NCC Online ↗

(1) A sign, to alert persons that the operation of certain doors must not be impaired, must be installed where it can readily be seen on, or adjacent to—

a required —

fire door providing direct access to a fire-isolated exit, except a door providing direct egress from a sole-occupancy unit in a Class 2 or 3 building or Class 4 part of a building; and

smoke door; and

any door which is a—

fire door forming part of a horizontal exit; and

smoke door that swings in both directions; and

door leading from a fire isolated exit to a road or open space.

(2) A sign required by (1)(a) must be fixed on the side of the door that faces a person seeking egress and, if the door is fitted with a device for holding it in the open position, either a sign must be fixed on the wall adjacent to the doorway, or signs must be fixed to both sides of the door.

(3) A sign required by (1)(b) must be fixed on each side of the door.

(4) A sign referred to in (1) must be in capital letters not less than 20 mm high in a colour contrasting with the background and state the following:

For an automatic door held open by an automatic hold-open device—

FIRE SAFETY DOOR — DO NOT OBSTRUCT

For a self-closing door—

FIRE SAFETY DOOR

DO NOT OBSTRUCT

DO NOT KEEP OPEN

For a door discharging from a fire-isolated exit —

FIRE SAFETY DOOR — DO NOT OBSTRUCT

New in NCC 2025. No D3D28 in NCC 2022 Volume One; it may have moved or been renumbered.