Deemed-to-Satisfy Provision · NCC 2025 Volume One

D3D27 Re-entry from fire-isolated exits

Part D3 Construction of exits · NCC 2019: D2.22

Open D3D27 on NCC Online ↗

(1) Doors of a fire-isolated exit must not be locked from the inside as follows:

In a Class 2 building.

In a Class 3 building.

In a Class 6 building.

In a Class 7a building.

In a Class 9 building.

In a fire-isolated exit serving any storey above an effective height of 25 m, throughout the exit.

(2) The requirements of (1) do not apply to a door, other than a door in a Class 9b early childhood centre, fitted with a fail-safe device that automatically unlocks the door upon the activation of a fire alarm and—

re-entry is facilitated by—

on at least every fourth storey, the doors are not able to be locked and a sign is fixed on such doors stating that re-entry is available; and

on at least every second storey where re-entry is not available, a sign is fixed to the wall within the fire-isolated exit within 1.5 m of the exit door stating the location of nearby re-entry; or

an intercommunication system, or an audible or visual alarm system, operated from within the enclosure is provided near the doors on at least every fourth storey, and a sign is fixed adjacent to such doors explaining its purpose and method of operation, and on at least every second storey where re-entry is not available, a sign is fixed to the wall within the fire-isolated exit within 1.5 m of the exit door stating the location of a nearby intercommunication system.

(3) The requirements of (1)(e) do not apply to a door in a Class 9b early childhood centre fitted with a fail-safe device that automatically unlocks the door upon the activation of a fire alarm.

Changed since NCC 2022. See NCC 2022 Volume One D3D27, or show what changed.

(1) Doors of a fire-isolated exit must not be locked from the inside as follows: In a Class 9a health-care 2 building. In a Class 9b early childhood centre. 3 building. In a Class 9c 6 building. In a Class 7a building. In a Class 9 building. In a fire-isolated exit serving any storey above an effective height of 25 m, throughout the exit. (2) The requirements of (1)(a), (c) and (d) (1) do not apply to a door, other than a door in a Class 9b early childhood centre, fitted with a fail-safe device that automatically unlocks the door upon the activation of a fire alarm and — re-entry is facilitated by — on at least every fourth storey, the doors are … is fixed on such doors stating that re-entry is available; and on at least every second storey where re-entry is not available, a sign is fixed to the wall within the fire-isolated exit within 1.5 m of the exit door stating the location of nearby re-entry; or an intercommunication system, or an audible or visual alarm system, operated from within the enclosure is provided near the doors on at least every fourth storey, and a sign is fixed adjacent to such doors explaining its purpose and method of operation. operation, and on at least every second storey where re-entry is not available, a sign is fixed to the wall within the fire-isolated exit within 1.5 m of the exit door stating the location of a nearby intercommunication system. (3) The requirements of (1)(b) (1)(e) do not apply to a door in a Class 9b early childhood centre fitted with a fail-safe device that automatically unlocks the door serving the Class 9b early childhood centre upon the activation of a fire alarm.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet D3D27? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →