D3D29 Protection of openable windows
Part D3 Construction of exits · NCC 2019: D2.24
(1) A window opening must be provided with protection, if the floor below the window is 2 m or more above the surface beneath in—
a bedroom in a Class 2 or 3 building or Class 4 part of a building; or
a Class 9b early childhood centre.
(2) Where the lowest level of the window opening is less than 1.7 m above the floor, a window opening covered by (1) must comply with the following:
The openable portion of the window must be protected with—
a device capable of restricting the window opening; or
a screen with secure fittings.
A device or screen required by (a) must—
not permit a 125 mm sphere to pass through the window opening or screen; and
resist an outward horizontal action of 250 N against the—
window restrained by a device; or
screen protecting the opening; and
have a child resistant release mechanism if the screen or device is able to be removed, unlocked or overridden.
(3) A barrier with a height not less than 865 mm above the floor is required to an openable window—
in addition to window protection, when a child resistant release mechanism is required by (2)(b)(iii); and
where the floor below the window is 4 m or more above the surface beneath if the window is not covered by (1).
(4) A barrier covered by (3) except for (5) must not—
permit a 125 mm sphere to pass through it; and
have any horizontal or near horizontal elements between 150 mm and 760 mm above the floor that facilitate climbing.
(5) A barrier required by (3) to an openable window in—
fire-isolated stairways, fire-isolated ramps and other areas used primarily for emergency purposes, excluding external stairways and external ramps; and
Class 7 (other than carparks) and Class 8 buildings and parts of buildings containing those classes,
must not permit a 300 mm sphere to pass through it.