Deemed-to-Satisfy Provision · NCC 2025 Volume One

D3D29 Protection of openable windows

Part D3 Construction of exits · NCC 2019: D2.24

Open D3D29 on NCC Online ↗

(1) A window opening must be provided with protection, if the floor below the window is 2 m or more above the surface beneath in—

a bedroom in a Class 2 or 3 building or Class 4 part of a building; or

a Class 9b early childhood centre.

(2) Where the lowest level of the window opening is less than 1.7 m above the floor, a window opening covered by (1) must comply with the following:

The openable portion of the window must be protected with—

a device capable of restricting the window opening; or

a screen with secure fittings.

A device or screen required by (a) must—

not permit a 125 mm sphere to pass through the window opening or screen; and

resist an outward horizontal action of 250 N against the—

window restrained by a device; or

screen protecting the opening; and

have a child resistant release mechanism if the screen or device is able to be removed, unlocked or overridden.

(3) A barrier with a height not less than 865 mm above the floor is required to an openable window—

in addition to window protection, when a child resistant release mechanism is required by (2)(b)(iii); and

where the floor below the window is 4 m or more above the surface beneath if the window is not covered by (1).

(4) A barrier covered by (3) except for (5) must not—

permit a 125 mm sphere to pass through it; and

have any horizontal or near horizontal elements between 150 mm and 760 mm above the floor that facilitate climbing.

(5) A barrier required by (3) to an openable window in—

fire-isolated stairways, fire-isolated ramps and other areas used primarily for emergency purposes, excluding external stairways and external ramps; and

Class 7 (other than carparks) and Class 8 buildings and parts of buildings containing those classes,

must not permit a 300 mm sphere to pass through it.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One D3D29.
Can't meet D3D29? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →

Defined terms used