Deemed-to-Satisfy Provision · NCC 2025 Volume One

D4D2 General building access requirements

Part D4 Access for people with a disability · NCC 2019: D3.1, Table D3.1

Open D4D2 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) Buildings and parts of buildings must be accessible as required by this clause, unless exempted by D4D5.

(2) Access requirements for a Class 1b building are as follows:

Dwellings located on one allotment and used for short-term holiday accommodation — to and within a number of dwellings determined in accordance with Table D4D2a.

A boarding house, bed and breakfast, guest house, hostel or the like, other than those described in (a) — to and within—

one bedroom and associated sanitary facilities; and

not less than one of each type of room or space for use in common by the residents or guests, including a cooking facility, sauna, gymnasium, swimming pool, laundry, games room, eating area, or the like; and

rooms or spaces for use in common by all residents on a floor to which access by way of a ramp complying with AS 1428.1 or a passenger lift is provided.

(3) For the purposes of (2)(a), a community or strata-type subdivision or development is considered to be on a single allotment.

(4) For a Class 2 building, common areas are to be accessible as follows:

From a pedestrian entrance required to be accessible to at least one floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level.

To and within not less than one of each type of room or space for use in common by the residents, including a cooking facility, sauna, gymnasium, swimming pool, common laundry, games room, individual shop, eating area, or the like.

Where a ramp complying with AS 1428.1 or a passenger lift is installed—

to the entrance doorway of each sole-occupancy unit; and

to and within rooms or spaces for use in common by the residents.

The requirements of (c) only apply where the space referred to in (c)(i) or (ii) is located on the levels served by the lift or ramp.

(5) For a Class 3 building, access requirements are as follows:

Common areas:

From a pedestrian entrance required to be accessible to at least one floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level.

To and within not less than one of each type of room or space for use in common by the residents, including a cooking facility, sauna, gymnasium, swimming pool, common laundry, games room, TV room, individual shop, dining room, public viewing area, ticket purchasing service, lunch room, lounge room, or the like.

Where a ramp complying with AS 1428.1 or a passenger lift is installed—

to the entrance doorway of each sole-occupancy unit; and

to and within rooms or spaces for use in common by the residents.

The requirements of (iii) only apply where the space referred to in (iii)(A) or (iii)(B) is located on the levels served by the lift or ramp.

To and within sole-occupancy units — in accordance with Table D4D2b.

(6) For Class 5, 6, 7b, 8 and 9a buildings, access must be provided to and within all areas normally used by the occupants.

(7) For a Class 7a building, access must be provided to and within any level containing accessible carparking spaces.

(8) For a Class 9b building, access requirements are as follows:

Schools and early childhood centres — to and within all areas normally used by the occupants.

An assembly building, not being a school or early childhood centre — to and within—

wheelchair seating spaces provided in accordance with D4D10; and

all other areas normally used by the occupants, except that access need not be provided to tiers or platforms of seating areas that do not contain wheelchair seating spaces.

(9) For a Class 9c building, access requirements are as follows:

Common areas:

From a pedestrian entrance required to be accessible to at least one floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level.

To and within not less than one of each type of room or space for use in common by the residents, including a cooking facility, sauna, gymnasium, swimming pool, common laundry, games room, TV room, individual shop, dining room, public viewing area, ticket purchasing service, lunch room, lounge room, or the like.

Where a ramp complying with AS 1428.1 or a passenger lift is installed—

to the entrance doorway of each sole-occupancy unit; and

to and within rooms or spaces for use in common by the residents.

The requirements of (iii) only apply where the space referred to in (iii)(A) or (iii)(B) is located on the levels served by the lift or ramp.

Sole-occupancy units — to and within a number of sole-occupancy units determined in accordance with Table D4D2b.

(10) For a Class 10 building, access requirements are as follows:

For a Class 10a non-habitable building located in an accessible area intended for use by the public and containing a sanitary facility, change room facility or shelter, to and within—

an accessible sanitary facility; and

a change room facility; and

a public shelter or the like.

For Class 10b swimming pools, to and into swimming pools with a total perimeter greater than 40 m, associated with a Class 1b, 2, 3, 5, 6, 7, 8 or 9 building that is required to be accessible, but not swimming pools for the exclusive use of occupants of a Class 1b building or a sole-occupancy unit in a Class 2 or Class 3 building.

Table D4D2a Requirements for access for people with a disability – sole-occupancy units in a Class 1b building

Total number of dwellings

Number required to be accessible

4 to 10

1

11 to 40

2

41 to 60

3

61 to 80

4

81 to 100

5

More than 100

5 dwellings plus 1 additional dwelling for each additional 30 dwellings or part thereof in excess of 100 dwellings.

Table D4D2b Requirements for access for people with a disability – sole-occupancy units in a Class 3 or 9c building

Total number of sole-occupancy units

Number required to be accessible

1 to 10

1

11 to 40

2

41 to 60

3

61 to 80

4

81 to 100

5

101 to 200

5 sole-occupancy units plus 1 additional sole-occupancy unit for each additional 25 units or part thereof in excess of 100.

201 to 500

9 sole-occupancy units plus 1 additional sole-occupancy unit for each additional 30 units or part thereof in excess of 200.

More than 500

19 sole-occupancy units plus 1 additional sole-occupancy unit for each additional 50 units or part thereof in excess of 500.

Table Notes

In a Class 3 building, not more than 2 required accessible sole-occupancy units may be located adjacent to each other.

In a Class 3 or 9c building where more than 2 accessible sole-occupancy units are required, they must be representative of the range of rooms available.

Tables

Changed since NCC 2022. See NCC 2022 Volume One D4D2, or show what changed.

(1) Buildings and parts of buildings must be accessible as … than those described in (a) — to and within — 1 one bedroom and associated sanitary facilities; and not less than 1 one of each type of room or space for use in … a pedestrian entrance required to be accessible to at least 1 one floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level. To and within not less than 1 one of each type of room or space for use in … a pedestrian entrance required to be accessible to at least 1 one floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level. To and within not less than 1 one of each type of room or space for use in … of (iii) only apply where the space referred to in (A) and (B) are (iii)(A) or (iii)(B) is located on the levels served by the lift or ramp. … a pedestrian entrance required to be accessible to at least 1 one floor containing sole-occupancy units and to the entrance doorway of each sole-occupancy unit located on that level. To and within not less than 1 one of each type of room or space for use in … they must be representative of the range of rooms available.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet D4D2? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →

State and territory variations all clauses side by side →

Clauses referred to

Defined terms used