D4D3 Access to buildings
Part D4 Access for people with a disability · NCC 2019: D3.2
(1) An accessway must be provided to a building required to be accessible —
from the main points of a pedestrian entry at the allotment boundary; and
from another accessible building connected by a pedestrian link; and
from any required accessible carparking space on the allotment.
(2) In a building required to be accessible, an accessway must be provided through the principal pedestrian entrance, and—
through not less than 50% of all pedestrian entrances including the principal pedestrian entrance; and
in a building with a total floor area more than 500 m2, a pedestrian entrance which is not accessible must not be located more than 50 m from an accessible pedestrian entrance,
except for pedestrian entrances serving only areas exempted by D4D5.
(3) Where a pedestrian entrance required to be accessible has multiple doorways—
if the pedestrian entrance consists of not more than 3 doorways — not less than 1 of those doorways must be accessible; and
if a pedestrian entrance consists of more than 3 doorways — not less than 50% of those doorways must be accessible.
(4) For the purposes of (3)—
an accessible pedestrian entrance with multiple doorways is considered to be one pedestrian entrance where—
all doorways serve the same part or parts of the building; and
the distance between each doorway is not more than the width of the widest doorway at that pedestrian entrance (see Figure D4D3); and
a doorway is considered to be the clear, unobstructed opening created by the opening of one or more door leaves (see Figure D4D3).
(5) Where a doorway on an accessway has multiple leaves (except an automatic opening door), one of those leaves must have a clear opening width of not less than 850 mm in accordance with AS 1428.1.
Figure D4D3 Doorways and pedestrian entrances for access purposes