E2D10 Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
Part E2 Smoke hazard management · NCC 2019: NSW Table E2.2a, Table E2.2a
(1) In a Class 7 or 8 building of not more than 25 m in effective height, and which does not exceed 18 000 m2 in floor area nor exceed 108 000 m3 in volume, the building must be provided with—
a sprinkler system complying with Specification 17, and provided with perimeter vehicular access complying with C3D5(2); or
an automatic fire detection and alarm system complying with AS 1670.1 and monitored in accordance with S20C8; or
an automatic smoke exhaust system in accordance with Specification 21; or
automatic smoke-and-heat vents in accordance with Specification 22; or
natural smoke venting, with ventilation openings distributed as evenly as practicable and comprising permanent openings at roof level with a free area not less than 1.5% of floor area and low level openings which may be permanent or readily openable with a free area not less than 1.5% of floor area.
(2) In a Class 5, 6, 7, 8 or 9 building of not more than 25 m in effective height, and which exceeds 18 000 m2 in floor area or 108 000 m3 in volume, the building must be provided with—
if the ceiling height of the fire compartment is not more than 12 m—
an automatic smoke exhaust system in accordance with Specification 21; or
automatic smoke-and-heat vents in accordance with Specification 22; or
if the ceiling height of the fire compartment is more than 12 m, an automatic smoke exhaust system in accordance with Specification 21.
(3) For the purposes of (1) and (2), reference to ‘the building’ being provided with specified measures, means to the nominated classes within the building.
Notes
Refer to E2D14 to E2D20 for specific provisions applicable to a Class 6 (in a fire compartment having a floor area of more than 2000 m2) and Class 9b building or part of a building.
Refer to E2D5 and E2D8 where a Class 5, 6, 7b, 8 and 9b building contains a Class 2, 3 or 4 part.
State and territory variations all clauses side by side →
Clauses referred to
- C3D5 Requirements for open spaces and vehicular access
- S20C8 System monitoring
- E2D14 Class 6 buildings – in fire compartments more than 2000 m2: Class 6 building (not containing an enclosed common walkway or mall serving more than one Class 6 sole-occupancy unit)
- E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
- E2D5 Buildings more than 25 m in effective height: Class 2 and 3 buildings and Class 4 parts of a building
- E2D8 Buildings not more than 25 m in effective height: Class 2 and 3 buildings and Class 4 part of a building