Specification clause · NCC 2025 Volume One

S20C8 System monitoring

Specification 20 Smoke detection and alarm systems · NCC 2019: VIC Spec E2.2a: 8, NSW Spec E2.2a: 8, Spec E2.2a: 8

Open S20C8 on NCC Online ↗
Varied in NSW. Check the variation for your state.

The following installations must be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with AS 1670.3:

A smoke detection system in a Class 3 building provided in accordance with S20C2(b)(i) or S20C2(b)(ii).

A smoke detection system in a Class 9a health-care building, if the building accommodates more than 20 patients.

A smoke detection system in a Class 9c building.

Smoke detection in accordance with S20C6 provided to activate—

a smoke exhaust system in accordance with Specification 21; or

smoke-and-heat vents in accordance with Specification 22.

An automatic fire detection and alarm system required by E2D10 for large isolated buildings subject to C3D4.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S20C8.