S20C8 System monitoring
Specification 20 Smoke detection and alarm systems · NCC 2019: VIC Spec E2.2a: 8, NSW Spec E2.2a: 8, Spec E2.2a: 8
The following installations must be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with AS 1670.3:
A smoke detection system in a Class 3 building provided in accordance with S20C2(b)(i) or S20C2(b)(ii).
A smoke detection system in a Class 9a health-care building, if the building accommodates more than 20 patients.
A smoke detection system in a Class 9c building.
Smoke detection in accordance with S20C6 provided to activate—
a smoke exhaust system in accordance with Specification 21; or
smoke-and-heat vents in accordance with Specification 22.
An automatic fire detection and alarm system required by E2D10 for large isolated buildings subject to C3D4.
State and territory variations all clauses side by side →
Clauses referred to
- S20C2 Type of system
- S20C6 Smoke detection for smoke control systems
- E2D10 Buildings not more than 25 m in effective height: large isolated buildings subject to C3D4
- C3D4 Large isolated buildings