E2D3 General requirements
Part E2 Smoke hazard management · NCC 2019: E2.2
(1) An air-handling system which does not form part of a smoke hazard management system in accordance with E2D4 to E2D20 and which recycles air from one fire compartment to another fire compartment or operates in a manner that may unduly contribute to the spread of smoke from one fire compartment to another fire compartment must, subject to (2), be designed and installed—
to operate as a shutdown system in accordance with AS 1668.1; or
such that it—
incorporates smoke dampers complying with AS 1668.1 where the air-handling ducts penetrate any elements separating the fire compartments served; and
is arranged such that the air-handling system is shut down and the smoke dampers are activated to close automatically by smoke detectors complying with clause 7.5 of AS 1670.1.
(2) For the purposes of (1), each sole-occupancy unit in a Class 2 or 3 building is treated as a separate fire compartment.
(3) Miscellaneous air-handling systems covered by Sections 5 and 6 of AS 1668.1 serving more than one fire compartment (other than a carpark ventilation system) and not forming part of a smoke hazard management system must comply with these Sections of the Standard.
(4) A smoke detection system must be installed in accordance with S20C6 to operate AS 1668.1 systems that are provided for zone pressurisation and automatic air pressurisation for fire-isolated exits.
Changed since NCC 2022. See NCC 2022 Volume One E2D3, or show what changed.
(1) An air-handling system which does not form part of … (2), be designed and installed — to operate as a smoke control shutdown system in accordance with AS 1668.1; or such that it — incorporates smoke dampers complying with AS 1668.1 where the air-handling ducts penetrate any elements separating the fire … for zone pressurisation and automatic air pressurisation for fire-isolated exits.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Clauses referred to
- E2D4 Fire-isolated exits
- E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
- S20C6 Smoke detection for smoke control systems