Deemed-to-Satisfy Provision · NCC 2025 Volume One

F6D4 Natural light borrowed from adjoining room

Part F6 Light and ventilation · NCC 2019: F4.3

Open F6D4 on NCC Online ↗

(1) Natural light to a room in a Class 2 building or Class 4 part of a building or in a sole-occupancy unit of a Class 3 building, may come through one or more glazed panels or openings from an adjoining room (including an enclosed verandah) if—

both rooms are within the same sole-occupancy unit or the enclosed verandah is on common property; and

the glazed panels or openings have an aggregate light transmitting area of not less than 10% of the floor area of the room to which it provides light; and

the adjoining room has—

windows, excluding roof lights, that—

have an aggregate light transmitting area of not less than 10% of the combined floor areas of both rooms; and

are open to the sky or face a court or other space open to the sky or an open verandah, carport or the like; or

roof lights, that—

have an aggregate light transmitting area of not less than 3% of the combined floor areas of both rooms; and

are open to the sky; or

a proportional combination of windows and roof lights required by (i) and (ii).

(2) The areas specified in (1)(b) and (c) may be reduced as appropriate if direct natural light is provided from another source.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F6D4.
Can't meet F6D4? A Performance Solution must meet the Performance Requirements it satisfies: F6P1, F6P2, F6P3, F6P4, F6P5. Start a Performance Solution →