Deemed-to-Satisfy Provision · NCC 2025 Volume One

F6D5 Artificial lighting

Part F6 Light and ventilation · NCC 2019: F4.4

Open F6D5 on NCC Online ↗

(1) Artificial lighting must be provided—

in required stairways, passageways, and ramps; and

if natural light of a standard equivalent to that required by F6D3 is not available, and the periods of occupation or use of the room or space will create undue hazard to occupants seeking egress in an emergency, in—

a Class 4 part of a building — to sanitary compartments, bathrooms, shower rooms, airlocks and laundries; and

a Class 2 building — to sanitary compartments, bathrooms, shower rooms, airlocks, laundries, common stairways and other spaces used in common by the occupants of the building; and

Class 3, 5, 6, 7, 8 and 9 buildings — to all rooms that are frequently occupied, all spaces required to be accessible, all corridors, lobbies, internal stairways, other circulation spaces and paths of egress.

(2) The artificial lighting system must comply with AS/NZS 1680.0.

(3) The system may provide a lesser level of illumination to the following spaces during times when the level of lighting would be inappropriate for the use:

A theatre, cinema or the like, when performances are in progress, with the exception of aisle lighting required by Part I1.

A museum, gallery or the like, where sensitive displays require low lighting levels.

A discotheque, nightclub or the like, where to create an ambience and character for the space, low lighting levels are used.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F6D5.
Can't meet F6D5? A Performance Solution must meet the Performance Requirements it satisfies: F6P1, F6P2, F6P3, F6P4, F6P5. Start a Performance Solution →