F6V3 Verification of suitable provision of natural light
Part F6 Light and ventilation · NCC 2019: FV4.3
Compliance with F6P1 is verified for the provision of natural light when the average daylight factor for each window is determined in accordance with the formula: [formula] , where—
[formula] = the net area of the light transmitting window (m2); and
[formula] = the total area of the internal wall, floor and ceiling surfaces (m2); and
[formula] = the diffuse light transmittance of the window; and
[formula] = visible sky angle in degrees, measured in a vertical plane normal to and from the centre of the window; and
[formula] = the area-weighted average reflectance of area [formula] .
Applications
F6V3 only applies to—
habitable rooms of Class 2 buildings and Class 4 parts of buildings; and
bedrooms and dormitories of Class 3 buildings; and
rooms used for sleeping purposes in Class 9a and 9c buildings; and
general purpose classrooms in primary and secondary school and playrooms or the like for the use of children in an early childhood centre in Class 9b buildings.