Verification Method · NCC 2025 Volume One

F6V3 Verification of suitable provision of natural light

Part F6 Light and ventilation · NCC 2019: FV4.3

Open F6V3 on NCC Online ↗

Compliance with F6P1 is verified for the provision of natural light when the average daylight factor for each window is determined in accordance with the formula: [formula] , where—

[formula] = the net area of the light transmitting window (m2); and

[formula] = the total area of the internal wall, floor and ceiling surfaces (m2); and

[formula] = the diffuse light transmittance of the window; and

[formula] = visible sky angle in degrees, measured in a vertical plane normal to and from the centre of the window; and

[formula] = the area-weighted average reflectance of area [formula] .

Applications

F6V3 only applies to—

habitable rooms of Class 2 buildings and Class 4 parts of buildings; and

bedrooms and dormitories of Class 3 buildings; and

rooms used for sleeping purposes in Class 9a and 9c buildings; and

general purpose classrooms in primary and secondary school and playrooms or the like for the use of children in an early childhood centre in Class 9b buildings.