Deemed-to-Satisfy Provision · NCC 2025 Volume One

G3D3 Separation of atrium by bounding walls

Part G3 Atrium construction · NCC 2019: G3.3

Open G3D3 on NCC Online ↗

An atrium must be separated from the remainder of the building at each storey by bounding walls set back not more than 3.5 m from the perimeter of the atrium well except in the case of the walls at not more than 3 consecutive storeys if—

one of those storeys is at a level at which direct egress to a road or open space is provided; and

the sum of the floor areas of those storeys that are contained within the atrium is not more than the maximum area that is permitted in Table C3D3.

New in NCC 2025. No G3D3 in NCC 2022 Volume One; it may have moved or been renumbered.