Deemed-to-Satisfy Provision · NCC 2025 Volume One

G3D4 Construction of bounding walls

Part G3 Atrium construction · NCC 2019: G3.4

Open G3D4 on NCC Online ↗

Bounding walls must—

have an FRL of not less than 60/60/60, and—

extend from the floor of the storey to the underside of the floor next above or to the underside of the roof; and

have any door openings protected with self-closing or automatic –/60/30 fire doors; or

be constructed of fixed toughened safety glass, or wired safety glass in non-combustible frames, with—

any door openings fitted with a self-closing smoke door complying with Specification 12; and

the walls and doors protected with wall-wetting systems in accordance with Specification 31; and

a fire barrier with an FRL of not less than –/60/30 installed in any ceiling spaces above the wall.

New in NCC 2025. No G3D4 in NCC 2022 Volume One; it may have moved or been renumbered.