NCC 2025 Volume One
Part G3 Atrium construction
8 clauses · Open on NCC Online ↗
- G3D1 Application of PartThis Part does not apply to an atrium which— connects only 2 storeys; or connects only 3 storeys if— each storey is provided with a sprinkler system…
- G3D2 Dimensions of atrium wellAn atrium well must have a width throughout the well that is able to contain a cylinder having a horizontal diameter of not less than 6 m.
- G3D3 Separation of atrium by bounding wallsAn atrium must be separated from the remainder of the building at each storey by bounding walls set back not more than 3.5 m from the perimeter of…
- G3D4 Construction of bounding wallsBounding walls must— have an FRL of not less than 60/60/60, and— extend from the floor of the storey to the underside of the floor next above or to…
- G3D5 Construction at balconiesIf a bounding wall separating an atrium from the remainder of the building is set back from the perimeter of the atrium well, a barrier that is…
- G3D6 Separation at roofIn an atrium — the roof must have the FRL prescribed in Table S5C11g; or the roof structure and membrane must be protected by a sprinkler system…
- G3D7 Means of egressAll areas within an atrium must have access to at least 2 exits.
- G3D8 Fire and smoke control systemsSprinkler systems, smoke control systems, fire detection and alarm systems, and emergency warning and intercom systems must be installed in…