NSW G5D2 Application of Part
NSW Part G5 Construction in bushfire prone areas · varies G5D2 Application of Part
Delete clause G5D2 and insert NSW G5D2 as follows:
The Deemed-to-Satisfy Provisions of this Part apply in a designated bushfire prone area to—
a Class 2 or 3 building; or
a Class 4 part of a building; or
a Class 9 building that is a special fire protection purpose —
located in an area subject to radiant heat levels of not greater than 10kW/m2 (calculated at 1200k), determined in accordance with Planning for Bush Fire Protection; or
where the development consent or a bushfire safety authority issued under Section 100B of the Rural Fires Act 1997 states that the Deemed-to-Satisfy Provisions apply; or
a Class 10a building or deck immediately adjacent or connected to a building or part of a type in (a), (b) or (c).
Notes
If a building of a type listed in (c) or (d) where associated with a building listed in (c) is subject to a radiant heat levels of greater than 10kW/m2 (calculated at 1200K), the building would need to comply with Performance Requirement NSW G5P2 by means of a Performance Solution. Unless the development consent or a bushfire safety authority issued under section 100B of the Rural Fires Act 1997 has stated that the Deemed-to-Satisfy Provisions of this part can apply.
Other than the circumstances listed in (1) there are no Deemed-to-Satisfy Provisions for buildings of the types listed in (c) or (d) where associated with a building listed in (c).
Changed since NCC 2022. See NCC 2022 Volume One NSW G5D2, or show what changed.
Delete clause G5D2 and insert NSW G5D2 as follows: The … Class 9 building that is a special fire protection purpose — located in an area subject to a Bushfire Attack Level (BAL) radiant heat levels of not exceeding BAL —12.5, greater than 10kW/m2 (calculated at 1200k), determined in accordance with Planning for Bush Fire Protection; or where the development consent or a bushfire safety authority issued under Section 100B of the Rural Fires Act 1997 states that the Deemed-to-Satisfy Provisions apply; or a Class 10a building or deck immediately adjacent or … with a building listed in (c) is subject to a BAL exceeding BAL —12.5, radiant heat levels of greater than 10kW/m2 (calculated at 1200K), the building would need to comply with Performance Requirement NSW G5P2 by means of a Performance Solution. There Unless the development consent or a bushfire safety authority issued under section 100B of the Rural Fires Act 1997 has stated that the Deemed-to-Satisfy Provisions of this part can apply. Other than the circumstances listed in (1) there are no Deemed-to-Satisfy Provisions for these buildings. buildings of the types listed in (c) or (d) where associated with a building listed in (c).