J3D10 Floors of a Class 4 part of a building
Part J3 Elemental provisions for a Class 4 part of a building
(1) Where a Class 4 part of a building has a concrete floor above an unenclosed carpark, undercroft or the like, underfloor insulation must be installed with an R-Value at least—
in climate zone 2 and climate zones 5 to 8, R2.0; and
in climate zones 3 and 4, R1.5.
(2) Where a Class 4 part of a building has a concrete floor above an enclosed carpark, undercroft or the like, underfloor insulation must be installed with an R-Value at least—
in climate zone 2, R0.5; and
in climate zones 4 and 5, R1.0; and
in climate zone 6, R1.5; and
in climate zones 7 and 8, R2.0.
(3) A concrete slab-on-ground, including a waffle-pod slab, with an in-slab or in-screed heating or cooling system must have insulation with an R-Value at least 1.0 installed around the vertical edge of its perimeter.
(4) A concrete slab-on-ground, other than a waffle-pod slab, must be insulated in accordance with the following:
In climate zones 6 and 7—
insulation with an R-Value of at least 0.64 must be installed around the vertical edge of its perimeter; and
insulation with an R-Value of at least 0.64 must be installed underneath the slab.
In climate zone 8—
insulation with an R-Value of at least 1.0 must be installed around the vertical edge of its perimeter; and
insulation with an R-Value of at least 2.0 must be installed underneath the slab.
(5) Insulation required by (3), (4)(a)(i) and (4)(b)(i) must—
be water resistant; and
be continuous from the adjacent finished ground level—
to a depth of not less than 300 mm; or
for at least the full depth of the vertical edge of the concrete slab-on-ground.
(6) The requirements of (3) do not apply to an in-screed heating or cooling system used solely in a bathroom, amenity area or the like.
Changed since NCC 2022. See NCC 2022 Volume One J3D10, or show what changed.
(1) Where a sole-occupancy unit of a Class 2 building or a Class 4 part of a building has a concrete floor above an unenclosed carpark, undercroft, undercroft or the like, underfloor insulation must be installed with an … in climate zones 3 and 4, R1.5. (2) Where a sole-occupancy unit of a Class 2 building or Class 4 part of a building has a concrete floor … in climate zones 7 and 8, R2.0. (3) A concrete slab-on-ground slab-on-ground, including a waffle-pod slab, with an in-slab or in-screed heating or cooling system must have insulation with an R-Value at least 1.0 installed around the vertical edge of tis its perimeter. (4) Except for A concrete slab-on-ground, other than a waffle-pod slab — slab, must be insulated in accordance with the following: In climate zones 6 and 7 — insulation with an R-Value … R-Value of at least 0.64 must be installed underneath the slab; and in slab. In climate zone 8 — insulation with an R-Value of at … used solely in a bathroom, amenity area or the like.
Removed words are struck through; added words are highlighted. Comparison of the text only.