J3D9 Wall-glazing construction of a Class 4 part of a building
Part J3 Elemental provisions for a Class 4 part of a building
(1) The Total System U-Value of wall-glazing construction that forms part of the external building fabric must not be greater than—
in climate zones 1 to 5, U2.2; or
in climate zone 6, U2.0; or
in climate zones 7 and 8, U1.4.
(2) The Total System U-Value of wall-glazing construction that forms part of the external building fabric must be calculated in accordance with Specification 37.
(3) Wall components of wall-glazing construction must achieve a minimum Total R-Value of—
where the wall is less than 80% of the area of the wall-glazing construction, R1.0; or
where the wall is 80% or more of the area of the wall-glazing construction, the value specified in Table J4D6b for a Class 3 building.
(4) In climate zones 1 to 6, the solar admittance of externally facing wall-glazing construction must be not greater than that shown in Table J3D 9.
(5) In climate zones 7 and 8, glazing in a wall-glazing construction must have a Total System SHGC of at least 0.4.
(6) The solar admittance of a wall-glazing construction must be calculated in accordance with Specification 37 as for a Class 3 building as required.
(7) The solar absorptance of an external wall must be in accordance with J3D8(3).
Table J3D9 Maximum wall-glazing construction solar admittance
Climate zone
Eastern aspect solar admittance
Northern aspect solar admittance
Southern aspect solar admittance
Western aspect solar admittance
1
0.10
0.10
0.14
0.10
2
0.10
0.10
0.10
0.10
3
0.11
0.11
0.11
0.11
4
0.11
0.11
0.11
0.11
5
0.13
0.13
0.13
0.13
6
0.14
0.14
0.14
0.14
7
N/A
N/A
N/A
N/A
8
N/A
N/A
N/A
N/A
Tables
Changed since NCC 2022. See NCC 2022 Volume One J3D9, or show what changed.
(1) The Total System U-Value of wall-glazing construction that forms … area of the wall-glazing construction, the value specified in Table J4D6a J4D6b for a Class 3 building. (4) In climate zones 1 … construction must be not greater than that shown in Table J3D9. J3D 9. (5) In climate zones 7 and 8, glazing in a … a wall-glazing construction must be calculated in accordance with Specification 37. 37 as for a Class 3 building as required. (7) The solar absorptance of an external wall must be … 7 N/A N/A N/A N/A 8 N/A N/A N/A N/A