J3D5 Roof thermal breaks of a Class 4 part of a building
Part J3 Elemental provisions for a Class 4 part of a building · NCC 2019: J0.4
(1) A metal-framed flat, skillion or cathedral roof that—
has metal sheet roofing directly fixed to metal purlins, metal rafters, metal battens or the like; and
does not have a ceiling lining or has a ceiling lining fixed directly to the metal purlins, metal rafters, metal battens or the like; and
has not achieved the required Total R-Value specified in Table J3D7t, calculated using a method that accounts for the effects of thermal bridging,
must have a thermal break, consisting of a material with an R-Value of greater than or equal to R0.2, installed within the structure.
(2) The requirements of (1) do not apply to roofs constructed using insulated sandwich panels.
Changed since NCC 2022. See NCC 2022 Volume One J3D5, or show what changed.
(1) A metal-framed flat, skillion or cathedral roof that — has metal sheet roofing directly fixed to metal purlins, metal rafters rafters, metal battens or metal battens; the like; and does not have a ceiling lining or has a ceiling lining fixed directly to those the metal purlins, metal rafters rafters, metal battens or metal battens, the like; and has not achieved the required Total R-Value specified in Table J3D7t, calculated using a method that accounts for the effects of thermal bridging, must have a thermal break, consisting of a material with an R-Value of greater than or equal to R0.2, installed between within the metal sheet roofing and its supporting metal purlins, metal rafters or metal battens. structure. (2) The requirements of (1) do not apply to roofs constructed using insulated sandwich panels.
Removed words are struck through; added words are highlighted. Comparison of the text only.