Deemed-to-Satisfy Provision · NCC 2025 Volume One

J4D4 Roof and ceiling construction

Part J4 Building fabric · NCC 2019: J1.3

Open J4D4 on NCC Online ↗

(1) A roof or ceiling must achieve a Total R-Value greater than or equal to—

for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area —

in climate zones 1, 2, 3, 4 and 5 — R3.7 for a downward direction of heat flow; and

in climate zone 6 — R3.2 for a downward direction of heat flow; and

in climate zone 7 — R3.7 for an upward direction of heat flow; and

in climate zone 8 — R4.8 for an upward direction of heat flow.

for a Class 3 or 9c building or a Class 9a ward area —

in climate zones 1, 3, 4 and 6 — R4.8 for a downward direction of heat flow; and

in climate zone 2 — R4.4 for a downward direction of heat flow; and

in climate zone 5 — R3.7 for a downward direction of heat flow; and

in climate zones 7 and 8 — R5.3 in an upward direction of heat flow.

(2) In climate zones 1, 2, 3, 4, 5, 6 and 7 the upper surface of a roof must have—

a Total Solar Reflectance greater than 0.55 and a thermal emittance greater than 0.85; or

a Solar Reflectance Index greater than 61; or

a solar absorptance of not more than 0.45 and a thermal emittance of greater than 0.85.

(3) In climate zones 1, 2, 3, 5 and 6 the upper surface of a metal roof, which has outside air intakes, unitary air-conditioning units or air-cooled chillers mounted on it or less than 2 m above it, must have—

a Total Solar Reflectance greater than 0.65 and a thermal emittance greater than 0.85; or

a Solar Reflectance Index greater than 80; or

a solar absorptance of not more than 0.35 and a thermal emittance of greater than 0.85.

(4) The requirements of (2) and (3) do not apply to the portion of the upper surface of a roof that is beneath a solar photovoltaic panel or a rooftop garden.

Changed since NCC 2022. See NCC 2022 Volume One J4D4, or show what changed.

(1) A roof or ceiling must achieve a Total R-Value greater than or equal to — for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area — in climate zones 1, 2, 3, 4 and 5, 5 — R3.7 for a downward direction of heat flow; and in climate zone 6, 6 — R3.2 for a downward direction of heat flow; and in climate zone 7, 7 — R3.7 for an upward direction of heat flow; and in climate zone 8, 8 — R4.8 for an upward direction of heat flow. for a Class 3 or 9c building or a Class 9a ward area — in climate zones 1, 3, 4 and 6 — R4.8 for a downward direction of heat flow; and in climate zone 2 — R4.4 for a downward direction of heat flow; and in climate zone 5 — R3.7 for a downward direction of heat flow; and in climate zones 7 and 8 — R5.3 in an upward direction of heat flow. (2) In climate zones 1, 2, 3, 4, 5, 6 and 7, 7 the upper surface of a roof must have — a Total Solar Reflectance greater than 0.55 and a thermal emittance greater than 0.85; or a Solar Reflectance Index greater than 61; or a solar absorptance of not more than 0.45 and a thermal emittance of greater than 0.85. (3) In climate zones 1, 2, 3, 5 and 6 the upper surface of a metal roof, which has outside air intakes, unitary air-conditioning units or air-cooled chillers mounted on it or less than 2 m above it, must have — a Total Solar Reflectance greater than 0.65 and a thermal emittance greater than 0.85; or a Solar Reflectance Index greater than 80; or a solar absorptance of not more than 0.35 and a thermal emittance of greater than 0.85. (4) The requirements of (2) and (3) do not apply to the portion of the upper surface of a roof must be not more than 0.45. that is beneath a solar photovoltaic panel or a rooftop garden.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet J4D4? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →