J6D13 Heat rejection equipment
Part J6 Air-conditioning and ventilation · NCC 2019: J5.12
(1) The motor rated power of a fan in a cooling tower, closed circuit cooler or evaporative condenser must not exceed the allowances in Table J6D13.
(2) The fan in an air-cooled condenser must have a motor rated power of not more than 42 W for each kW of heat rejected from the refrigerant when determined in accordance with AHRI 460.
(3) A fan with a three-phase motor in heat rejection equipment must be capable of variable speed operation.
(4) The requirements of (2) and (3) do not apply to—
a fan in a refrigerant chiller of an air-conditioning system that complies with J6D11; and
fans in unitary air-conditioning equipment, such as a packaged air-conditioners, a split system or a variable refrigerant flow unit that complies with J6D12; and
a fan in a 4-pipe chiller or air source heat pump water heater that complies with J6D10 (8).
Table J6D13 Maximum fan motor power – Cooling towers, closed circuit coolers and evaporative condensers
Type
Cooling tower maximum fan motor input power (W/kW)
Closed circuit cooler maximum fan motor input power (W/kW)
Evaporative condenser maximum fan motor input power (W/kW)
Induced draft
10.4
16.9
11.0
Forced draft
19.5
Note
11.0
Table Notes
A closed circuit, forced draft cooling tower must not be used.
Tables
Changed since NCC 2022. See NCC 2022 Volume One J6D13, or show what changed.
(1) The motor rated power of a fan in a … 42 W for each kW of heat rejected from the refrigerant, refrigerant when determined in accordance with AHRI 460 except for 460. (3) A fan with a three-phase motor in heat rejection equipment must be capable of variable speed operation. (4) The requirements of (2) and (3) do not apply to — a fan in a refrigerant chiller in of an air-conditioning system that complies with the energy efficiency ratios J6D11; and fans in J6D11; or unitary air-conditioning equipment, such as a packaged air-conditioners, a split systems, and system or a variable refrigerant flow air-conditioning equipment unit that complies with the energy efficiency ratios J6D12; and a fan in J6D12. a 4-pipe chiller or air source heat pump water heater that complies with J6D10 (8). Table J6D13 Maximum fan motor power – Cooling towers, closed circuit coolers and evaporative condensers Type Cooling tower maximum fan motor input power (W/kWrej) (W/kW) Closed circuit cooler maximum fan motor input power (W/kWrej) (W/kW) Evaporative condenser maximum fan motor input power (W/kWrej) (W/kW) Induced draft 10.4 16.9 11.0 Forced draft 19.5 Note 11.0 Table Notes A closed circuit, forced draft cooling tower must not be used.
Removed words are struck through; added words are highlighted. Comparison of the text only.