Deemed-to-Satisfy Provision · NCC 2025 Volume One

J7D8 Lifts

Part J7 Artificial lighting and power · NCC 2019: J6.7

Open J7D8 on NCC Online ↗

Lifts must—

be configured to ensure artificial lighting and ventilation in the car are turned off when it is unused for 15 minutes; and

achieve the idle and standby energy performance level in Table J7D8a; and

achieve—

the energy efficiency class in Table J7D8b; or

if a dedicated goods lift, energy efficiency class D in accordance with ISO 25745-2.

Table J7D8a Lift idle and standby energy performance level

Rated load

Idle and standby energy performance level in accordance with ISO 25745-2 Note

≤ 800 kg

2

> 800 kg to ≤ 2000 kg

3

> 2000 kg to ≤ 4000 kg

4

> 4000 kg

5

Table Notes

Applies to the standby power used after 30 minutes.

Table J7D8b Lift energy efficiency class

Usage category in accordance with ISO 25745-2

Energy efficiency class in accordance with ISO 25745-2

1-4

C

≥ 5

D

Tables

Changed since NCC 2022. See NCC 2022 Volume One J7D8, or show what changed.

Lifts must — be configured to ensure artificial lighting and … standby energy performance level in accordance with ISO 25745-2 Note Less than or equal to ≤ 800 kg 2 801 > 800 kg to less than or equal to ≤ 2000 kg 3 2001 > 2000 kg to less than or equal to ≤ 4000 kg 4 Greater than > 4000 kg 5 Table Notes Applies to the standby power … Energy efficiency class in accordance with ISO 25745-2 1-4 C > ≥ 5 D