J7D8 Lifts
Part J7 Artificial lighting and power · NCC 2019: J6.7
Lifts must—
be configured to ensure artificial lighting and ventilation in the car are turned off when it is unused for 15 minutes; and
achieve the idle and standby energy performance level in Table J7D8a; and
achieve—
the energy efficiency class in Table J7D8b; or
if a dedicated goods lift, energy efficiency class D in accordance with ISO 25745-2.
Table J7D8a Lift idle and standby energy performance level
Rated load
Idle and standby energy performance level in accordance with ISO 25745-2 Note
≤ 800 kg
2
> 800 kg to ≤ 2000 kg
3
> 2000 kg to ≤ 4000 kg
4
> 4000 kg
5
Table Notes
Applies to the standby power used after 30 minutes.
Table J7D8b Lift energy efficiency class
Usage category in accordance with ISO 25745-2
Energy efficiency class in accordance with ISO 25745-2
1-4
C
≥ 5
D
Tables
Changed since NCC 2022. See NCC 2022 Volume One J7D8, or show what changed.
Lifts must — be configured to ensure artificial lighting and … standby energy performance level in accordance with ISO 25745-2 Note Less than or equal to ≤ 800 kg 2 801 > 800 kg to less than or equal to ≤ 2000 kg 3 2001 > 2000 kg to less than or equal to ≤ 4000 kg 4 Greater than > 4000 kg 5 Table Notes Applies to the standby power … Energy efficiency class in accordance with ISO 25745-2 1-4 C > ≥ 5 D
Removed words are struck through; added words are highlighted. Comparison of the text only.