New South Wales variation · NCC 2025 Volume One

NSW D2D3 Number of exits required

NSW Part D2 Provision for escape · varies D2D3 Number of exits required

Open on NCC Online ↗

Delete subclause D2D3(4) and insert NSW D2D3(4) as follows:

(4) Class 9 buildings—

In addition to any horizontal exit, not less than 2 exits must be provided from the following:

Each storey if the building has a rise in storeys of more than 6 or an effective height of more than 25 m.

Any storey which includes a patient care area in a Class 9a health-care building.

Any storey that contains sleeping areas in a Class 9c building.

Any storey used as a Class 9b early childhood centre, or any Class 9b early childhood centre which forms part of a storey.

Each storey in a primary or secondary school with a rise in storeys of 2 or more.

Any storey or mezzanine that accommodates more than 50 persons, calculated under D2D18.

Any storey or mezzanine within an auditorium in an entertainment venue.

The requirements of (a) do not apply to a part of a storey that—

is a plant room, machinery room, storeroom, lift-machine room or the like; and

is provided with direct egress to a road, open space or a fire-isolated exit complying with D2D12(2); and

satisfies D2D5 by the provision of 1 exit.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One NSW D2D3.