D2D12 Travel via fire-isolated exits
Part D2 Provision for escape · NCC 2019: D1.7
(1) A doorway from a room must not open directly into a stairway, passageway or ramp that is required to be fire-isolated unless it is from—
a public corridor, public lobby or the like; or
a sole-occupancy unit occupying all of a storey; or
a sanitary compartment, airlock or the like.
(2) Each fire-isolated stairway or fire-isolated ramp must provide independent egress from each storey served and discharge directly, or by way of its own fire-isolated passageway —
to a road or open space; or
to a point—
in a storey or space, within the confines of the building, that is used only for pedestrian movement, car parking or the like and is open for at least ⅔ of its perimeter; and
from which an unimpeded path of travel, not further than 20 m, is available to a road or open space; or
into a covered area that—
adjoins a road or open space; and
is open for at least ⅓ of its perimeter; and
has an unobstructed clear height throughout, including the perimeter openings, of not less than 3 m; and
provides an unimpeded path of travel from the point of discharge to the road or open space of not more than 6 m.
(3) Where a path of travel from the point of discharge of a fire-isolated exit necessitates passing within 6 m of any part of an external wall of the same building, measured horizontally at right angles to the path of travel, the following applies:
That part of the wall must have—
an FRL of not less than 60/60/60; and
any openings protected internally in accordance with C4D5; and
The protection required by (a) must extend for a distance of 3 m above or below, as appropriate, the level of the path of travel, or for the height of the wall, whichever is the lesser.
(4) If more than 2 access doorways, not from a sanitary compartment or the like, open to a required fire-isolated exit in the same storey —
a smoke lobby in accordance with D3D7 must be provided; or
the exit must be pressurised in accordance with AS 1668.1.
(5) A ramp must be provided at any change in level less than 600 mm in a fire-isolated passageway in a Class 9 building.