Deemed-to-Satisfy Provision · NCC 2025 Volume One

D2D12 Travel via fire-isolated exits

Part D2 Provision for escape · NCC 2019: D1.7

Open D2D12 on NCC Online ↗

(1) A doorway from a room must not open directly into a stairway, passageway or ramp that is required to be fire-isolated unless it is from—

a public corridor, public lobby or the like; or

a sole-occupancy unit occupying all of a storey; or

a sanitary compartment, airlock or the like.

(2) Each fire-isolated stairway or fire-isolated ramp must provide independent egress from each storey served and discharge directly, or by way of its own fire-isolated passageway —

to a road or open space; or

to a point—

in a storey or space, within the confines of the building, that is used only for pedestrian movement, car parking or the like and is open for at least ⅔ of its perimeter; and

from which an unimpeded path of travel, not further than 20 m, is available to a road or open space; or

into a covered area that—

adjoins a road or open space; and

is open for at least ⅓ of its perimeter; and

has an unobstructed clear height throughout, including the perimeter openings, of not less than 3 m; and

provides an unimpeded path of travel from the point of discharge to the road or open space of not more than 6 m.

(3) Where a path of travel from the point of discharge of a fire-isolated exit necessitates passing within 6 m of any part of an external wall of the same building, measured horizontally at right angles to the path of travel, the following applies:

That part of the wall must have—

an FRL of not less than 60/60/60; and

any openings protected internally in accordance with C4D5; and

The protection required by (a) must extend for a distance of 3 m above or below, as appropriate, the level of the path of travel, or for the height of the wall, whichever is the lesser.

(4) If more than 2 access doorways, not from a sanitary compartment or the like, open to a required fire-isolated exit in the same storey —

a smoke lobby in accordance with D3D7 must be provided; or

the exit must be pressurised in accordance with AS 1668.1.

(5) A ramp must be provided at any change in level less than 600 mm in a fire-isolated passageway in a Class 9 building.

New in NCC 2025. No D2D12 in NCC 2022 Volume One; it may have moved or been renumbered.
Can't meet D2D12? A Performance Solution must meet the Performance Requirements it satisfies: D1P1, D1P2, D1P3, D1P4, D1P5, D1P6, D1P8, D1P10, D1P9. Start a Performance Solution →