NSW E2D19 Class 9b – assembly buildings: other assembly buildings (not listed in NSW E2D16 to E2D18)
NSW Part E2 Smoke hazard management · varies E2D19 Class 9b – assembly buildings: theatres and public halls (not listed in E2D18) including lecture theatres and cinema/auditorium complexes
Delete clause E2D19 and insert NSW E2D19 as follows:
(1) Unless otherwise described in (2), in a building or part of a building used as an assembly building (not being a night club, discotheque or the like; or an exhibition hall, museum or art gallery) where the floor area of the Class 9b part of a fire compartment is more than 2000 m2, the Class 9b building or part must be provided with—
an automatic smoke exhaust system complying with Specification 21; or
roof mounted automatic smoke-and-heat vents complying with Specification 22, in a single storey building or the top storey of a multi storey building; or
if the floor area of the fire compartment is not more than 5000 m2 and the building has a rise in storeys of not more than 2—
an automatic smoke detection and alarm system complying with Specification 20; or
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
(2) The following buildings are exempt from the provisions of (1):
Sporting complexes, (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than indoor sports stadiums with total spectator seating for more than 1000 persons.
Churches and other places used solely for religious worship.
School classrooms.
(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another Class.
Notes
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
Changed since NCC 2022. See NCC 2022 Volume One NSW E2D19, or show what changed.
Delete clause E2D19 and insert NSW E2D19 as follows: (1) … hall, museum or art gallery) where the floor area of the Class 9b part of a fire compartment is more than 2000 m2, the fire compartment Class 9b building or part must be provided with — an automatic smoke exhaust system … NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.
Removed words are struck through; added words are highlighted. Comparison of the text only.