New South Wales variation · NCC 2025 Volume One

NSW S20C8 System monitoring

NSW Specification 20 Smoke detection and alarm systems · varies S20C8 System monitoring

Open on NCC Online ↗

Delete clause S20C8 and insert NSW S20C8 as follows:

The following installations must be connected to a fire alarm monitoring system connected to a fire station or fire station dispatch centre in accordance with AS 1670.3:

A smoke detection system in a Class 3 building provided in accordance with S20C2(b)(i) or S20C2(b)(ii).

A smoke detection system in a Class 9a health-care building, if the building accommodates more than 20 patients.

A smoke detection system in a Class 9c building.

Smoke detection in accordance with S20C6 provided to activate—

a smoke exhaust system in accordance with Specification 21; or

smoke-and-heat vents in accordance with Specification 22.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One NSW S20C8.

The national clause