Specification clause · NCC 2025 Volume One

S13C2 Application

Specification 13 Penetration of walls, floors and ceilings by services · NCC 2019: Spec C3.15: 2

Open S13C2 on NCC Online ↗

(1) This Specification applies to installations permitted under the Deemed-to-Satisfy Provisions of the NCC as alternatives to systems that have been demonstrated by test to fulfil the requirements of C4D15(2)(a).

(2) This Specification does not apply to installations in ceilings required to have a resistance to the incipient spread of fire nor to the installation of piping that contains or is intended to contain a flammable liquid or gas.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S13C2.