Specification 13 Penetration of walls, floors and ceilings by services · NCC 2019: Spec C3.15: 3

Open S13C3 on NCC Online ↗

(1) A pipe system comprised entirely of metal (excluding pipe seals or the like) that is not normally filled with liquid must not be located within 100 mm, for a distance of 2 m from the penetration, of any combustible building element or a position where combustible material may be located, and must be constructed of—

copper alloy or stainless steel with a wall thickness of at least 1 mm; or

cast iron or steel (other than stainless steel) with a wall thickness of at least 2 mm.

(2) An opening for a pipe system comprised entirely of metal (excluding pipe seals or the like) must—

be neatly formed, cut or drilled; and

be no closer than 200 mm to any other service penetration; and

accommodate only one pipe.

(3) A pipe system comprised entirely of metal (excluding pipe seals or the like) must be wrapped but must not be lagged or enclosed in thermal insulation over the length of its penetration of a wall, floor or ceiling unless the lagging or thermal insulation fulfils the requirements of S13C7.

(4) The gap between a metal pipe and the wall, floor or ceiling it penetrates must be fire-stopped in accordance with S13C7.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S13C3.