Specification clause · NCC 2025 Volume One

S27C2 General requirements

Specification 27 Accessible adult change facilities · NCC 2019: Spec F2.9: 2

Open S27C2 on NCC Online ↗

(1) Each accessible adult change facility must—

be constructed so that all required equipment and fixtures are contained within the same room; and

if it is a unisex facility, be located such that it can be entered without crossing an area reserved for one sex only.

(2) In each accessible adult change facility, the following must be provided:

A hoist complying with S27C3.

A toilet pan, seat, backrest and grabrails complying with S27C4.

A washbasin and tap complying with S27C5.

Fixtures and fittings as specified in S27C6.

A change table complying with S27C7.

Changing rails complying with S27C8.

An automated sliding entrance door complying with S27C9.

Signage complying with S27C10.

Operating instructions for the hoist and change table in accordance with S27C11.

Circulation spaces complying with Figures S27C2a, S27C2b and S27C2c.

(3) The floor surface must have a slip resistance classification of not less than R10 or P3 when tested in accordance with AS 4586.

(4) For the purposes of Figures S27C2a, S27C2b and S27C2c, the following applies:

The Roman numerals shown in Figures S27C2a, S27C2b and S27C2c indicate the following required circulation spaces:

Turning space: a full circle of 1125 mm radius.

Each side of the pan: 900 mm (measured from each edge of the pan).

In front of the pan: 2350 mm (measured from the wall behind the pan, and therefore includes the pan itself).

For a washbasin: the width of the basin (450 mm) increasing to a width of 1350 mm measured at a distance of 750 mm out from the wall against which the washbasin is mounted then continuing at that width for a further 800 mm (to a total of 1550 mm out from the wall).

For changing rails: the width of the rails increasing to a width of 1350 mm at a distance of 750 mm out from the wall to which the rails are fixed then continuing at that width for a further 800 mm (to a total of 1550 mm out from the wall).

All required circulation spaces must extend for a minimum height of 2000 mm above finished floor level.

Required circulation spaces may be overlapped.

Figure S27C2a Required circulation spaces — Turning space, each side of the pan and in front of the pan

Figure S27C2b Required circulation spaces — Turning space and circulation space for a washbasin

Figure S27C2c Required circulation spaces — Turning space and circulation space for changing rails

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S27C2.