S34C2 Reference building
Specification 34 Modelling parameters for J1V3 · NCC 2019: Spec JVb: 2
The annual greenhouse gas emissions must be calculated for the reference building in accordance with the following:
The reference building must—
subject to (b), (c) and (d), comply with Deemed-to-Satisfy Provisions in Parts J4 to J8; and
have the minimum amount of mechanical ventilation required by Part F6; and
be provided with a solar photovoltaic system that complies with—
J9D5(2)(a), J9D5(3) and J9D5(4) with PV panels modelled as parallel to the roof and assuming an average solar photovoltaic panel power rating of 225 W/m2; or
J9D5(2)(b), J9D5(3) and J9D5(4).
The external walls must have a solar absorptance of 0.6.
The U-Value of the wall-glazing construction must be calculated according to S37C3.
The solar admittance of the wall-glazing construction must be calculated according to S37C5.
Where J1V3(1)(b)(i) or J1V3(1)(b)(ii) applies, the air-conditioning must—
for 95% of the annual hours of operation, achieve dry bulb temperatures between—
18°C to 25°C for conditioned spaces with transitory occupancy; and
subject to (ii), 21°C to 24°C in all other conditioned spaces; and
if the proposed building has no mechanically provided cooling or has mixed mode cooling, have the same method of control and control set points for non-mechanical cooling as the proposed building.
The infiltration rate in each zone must be—
0.7 air changes per hour throughout all zones when there is no mechanically supplied outdoor air; and
0.35 air changes per hour throughout all zones at all other times.
The artificial lighting must achieve the required maximum illumination power density in Part J7 without applying the control device adjustment factors.
Minimum Energy Performance Standards must be applied to services not covered by Parts J6 to J8.
Changed since NCC 2022. See NCC 2022 Volume One S34C2, or show what changed.
The annual greenhouse gas emissions must be calculated for the reference building in accordance with the following: The reference building must — subject to (b), (c) and (d), comply with Deemed-to-Satisfy Provisions in Parts J4 to J8; and have the minimum amount of mechanical ventilation required by Part F6. F6; and be provided with a solar photovoltaic system that complies with — J9D5(2)(a), J9D5(3) and J9D5(4) with PV panels modelled as parallel to the roof and assuming an average solar photovoltaic panel power rating of 225 W/m2; or J9D5(2)(b), J9D5(3) and J9D5(4). The external walls must have a solar absorptance of 0.6. The U-Value of the wall-glazing construction must be calculated according to S37C3. The solar admittance of the wall-glazing construction must be calculated according to S37C5. Where J1V3(1)(b)(i) or J1V3(1)(b)(ii) applies, the air-conditioning must — for 98% 95% of the annual hours of operation, achieve dry bulb temperatures between — 18°CDB 18°C to 25°CDB 25°C for conditioned spaces with transitory occupancy; and subject to (ii), 21°CDB 21°C to 24°CDB 24°C in all other conditioned spaces; and if the proposed building … applied to services not covered by Parts J6 to J8.
Removed words are struck through; added words are highlighted. Comparison of the text only.
Clauses referred to
- J9D5 Facilities for solar photovoltaic and battery systems
- S37C3 U-Value — Method 1 (Single Aspect)
- S37C5 Solar admittance — Method 1 (Single Aspect)
- J1V3 Verification using a reference building