Specification clause · NCC 2025 Volume One

S36C2 Construction Deemed-to-Satisfy

Specification 36 Material properties · NCC 2019: Spec J1.2: 2

Open S36C2 on NCC Online ↗

(1) Tables S36C2a, S36C2b, S36C2c, S36C2d and S36C2e list the thermal conductivity considered to be achieved by some common construction materials.

(2) For the purposes of Tables S36C2a, S36C2b, S36C2c, S36C2d and S36C2e:

For materials which incorporate cores or hollows in regular patterns (such as cored brickwork, hollow blockwork and cored floor or wall panels), the tabulated material densities and thermal conductivities are based on the gross density (mass divided by external dimensions).

The R-Value of a material is determined by dividing the thickness of the material in metres by the thermal conductivity in Wm-1K-1.

(3) Tables S36C2f, S36C2g, S36C2h, S36C2i, S36C2j, S36C2k, S36C2l and S36C2m list the R-Value considered to be achieved by air films and airspaces.

(4) For an envelope that contains a ventilated airspace, the Total R-Value of the building fabric must be reduced based on the area of ventilation openings in accordance with clause 6.3 of AS/NZS 4859.2.

(5) The requirements of (4) do not apply to a roof with an airspace greater than 300 mm or a pitched roof greater than 5° with a horizontal ceiling.

Table S36C2a Thermal conductivity of typical framing materials

Description

Density (kg/m3)

Thermal conductivity (Wm-1K-1)

Steel

7850

47.5

Timber – kiln dried hardwood (across the grain)

677

0.16

Timber – Radiata pine (across the grain)

506

0.12

Table S36C2b Thermal conductivity of typical roof cladding materials

Description

Density (kg/m3)

Thermal conductivity (Wm-1K-1)

Aluminium sheeting

2680

210

Concrete or terra cotta tiles

1922

0.81

Steel sheeting

7850

47.5

Table S36C2c Thermal conductivity of typical wall cladding materials

Description

Density (kg/m3)

Thermal conductivity (Wm-1K-1)

Aluminium sheeting

2680

210

Autoclaved aerated concrete

350

0.10

510

0.15

900

0.27

Cement render (1 part cement to 4 parts sand)

1570

0.53

Clay brick: 2.75 kg

1430

0.55

Clay brick: 3.25 kg

1690

0.65

Clay brick: 3.75 kg

1950

0.78

Concrete block: 190 mm dense or 90 mm dense solid

1100/2200

1.1

Concrete block: 140 mm dense or 190 mm lightweight

1250/910

0.85

Concrete block: 90 mm dense hollow or 90 mm lightweight solid

1650 / 1800

0.75

Concrete block: 140 mm lightweight

1050

0.67

Concrete block: 90 mm lightweight

1360

0.55

Fibre-cement

1360

0.25

Gypsum plasterboard

880

0.17

Pine weatherboards

506

0.10

Plywood

530

0.14

Solid concrete

2400

1.44

Steel sheeting

7850

47.5

Prestressed hollow core concrete panel

1680

0.80

Table S36C2d Thermal conductivity of typical flooring materials

Description

Density (kg/m3)

Thermal conductivity (Wm-1K-1)

Carpet underlay

-

0.04

Carpet

-

0.05

Prestressed hollow core concrete planks

1680

0.80

Particleboard

640

0.12

Plywood

530

0.14

Timber – kiln dried hardwood (across the grain)

677

0.16

Timber – Radiata pine (across the grain)

506

0.10

Solid concrete

2400

1.44

Vinyl floor tiles

2050

0.79

Table S36C2e Thermal conductivity of other materials not listed in Tables S36C2a to S36C2d

Description

Density (kg/m3)

Thermal conductivity (Wm-1K-1)

Clay soil (10% moisture content)

1300

0.6

PMMA (polymethylmethacrylate)

1180

1.0

Polycarbonates

1200

0.2

Sand (6% moisture content)

1800

1.64

Soda lime glass

2500

1.0

Table S36C2f Typical R-Values for air films: surfaces other than outdoor surfaces

Position of air film

Direction of heat flow

R-Value

On a surface with a pitch of not more than 5°

Up

0.11

Down

0.16

On a surface with a pitch of more than 5° but not more than 30°

Up

0.11

Down

0.15

On a surface with a pitch of more than 30° but not more than 45°

Up

0.11

Down

0.13

On a wall

Horizontal

0.12

Table S36C2g Typical R-Values for air films: outdoor surfaces

Position of air film

Direction of heat flow

R-Value

Any

Any

0.03

Table S36C2h Typical R-Values for airspaces: non-reflective non-ventilated

Position of airspace

Direction of heat flow

R-Value

In a roof with a pitch not more than 5° or cathedral ceiling with a 20 mm to 50 mm thick roof airspace

Up

0.15

Down

0.15

In a roof with a pitch not more than 5° or cathedral ceiling with a more than 50 mm to 300 mm thick roof airspace

Up

0.15

Down

0.17

In a roof airspace greater than 300 mm thick or with a horizontal ceiling and a roof pitch more than 5°

Up

0.18

Down

0.28

In a wall

Horizontal

0.16

Table Notes

Linear interpolation may be used to calculate the R-Value of the airspace in a roof with an intermediate pitch.

A non-ventilated airspace in a roof is one with continuous cover, such as metal or sarked tiles, and no specific provision for ventilation.

R-Values are calculated using AS/NZS 4859.2 based on the following:

summer temperatures of 24°C internally and 36°C externally for heat transfer down; and

winter temperatures of 18°C internally and 12°C externally for heat transfer up; and

average of summer and winter results for horizontal heat transfer (e.g. in walls).

A non-ventilated airspace in a wall is one where there is no express provision for airflow through it and openings to the external environment do not exceed more than 500 mm2 per metre of length in the horizontal direction.

A non-ventilated airspace in a wall for the purposes of Note (4) includes a wall with drainage openings or weepholes that are open vertical joints in the outer leaf of a cavity masonry wall, which are not regarded as ventilation openings.

Table S36C2i Typical R-Values for airspaces: reflective non-ventilated

Position of airspace

Direction of heat flow

R-Value

In a wall with an inner reflective surface of 0.05 emittance and a 20 mm to 100 mm airspace to the wall lining

Horizontal

0.61

In a wall with a central reflective membrane with an inner surface emittance of 0.05 and a 20 mm to 100 mm airspace from the membrane to the wall lining, and an outer anti-glare emittance of 0.08 and a 20 mm to 100 mm airspace to the wall cladding

Horizontal

1.1

In a wall with an outer anti-glare reflective surface of 0.08 emittance and a 20 mm to 100 mm airspace to the wall cladding

Horizontal

0.53

Table Notes

A non-ventilated airspace in a wall is one where there is no express provision for airflow through it and openings to the external environment do not exceed 500 mm2 per metre of length in the horizontal direction.

A non-ventilated airspace in a wall for the purposes of Note (1) includes a wall with drainage openings or weepholes that are open vertical joints in the outer leaf of a cavity masonry wall, which are not regarded as ventilation openings.

R-Values are calculated using AS/NZS 4859.2 based on the following:

summer temperatures of 24°C internally and 36°C externally for heat transfer down; and

winter temperatures of 18°C internally and 12°C externally for heat transfer up; and

average of summer and winter results for horizontal heat transfer (e.g. in walls); and

emittances are normal emittances of bounding surfaces in accordance with AS 4200.1.

Table S36C2j Typical R-Values for airspaces: non-reflective ventilated

Position of airspace

Direction of heat flow

R-Value

In a roof airspace greater than 300 mm thick or with a horizontal ceiling and a pitch more than 5°

Up

Nil

Down

0.46

Table S36C2k Typical R-Values for roof spaces with a reflective surface: Roof space > 300 mm thick or pitched roof with a horizontal ceiling

Direction of heat flow

R-Value of reflective airspace

Ventilated roof space

Non-ventilated roof space

Up

0.34

0.56

Down

1.36

1.09

Table Notes

A non-ventilated airspace in a roof is one with continuous cover, such as metal or sarked tiles, and no specific provision for ventilation.

A reflective surface is a surface with normal emittance of 0.05 or less, in accordance with AS 4200.1.

Table S36C2l Typical R-Values for non-ventilated roof spaces with a reflective surface: Flat, skillion or pitched roof (≤5°) with horizontal ceiling, roof space not more than 300 mm thick

Emittance of airspace bounding surfaces

Thickness of roof space

Direction of heat flow

R-Value of reflective airspace

Surface 1 emittance 0.9, Surface 2 emittance 0.05

≤ 300 mm

Up

0.43

Surface 1 emittance 0.9, Surface 2 emittance 0.05

20 mm

Down

0.60

Tables

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One S36C2.