Table S36C2l Typical R-Values for non-ventilated roof spaces with a reflective surface: Flat, skillion or pitched roof (≤5°) with horizontal ceiling, roof space not more than 300 mm thick

Specification 36 Material properties

Open Table S36C2l on NCC Online ↗
Emittance of airspace bounding surfacesThickness of roof spaceDirection of heat flowR-Value of reflective airspace
Surface 1 emittance 0.9, Surface 2 emittance 0.05≤ 300 mmUp0.43
Surface 1 emittance 0.9, Surface 2 emittance 0.0520 mmDown0.60
Surface 1 emittance 0.9, Surface 2 emittance 0.0560 mmDown1.16
Surface 1 emittance 0.9, Surface 2 emittance 0.05100 mm to ≤ 300 mmDown1.30

Table Notes

A non-ventilated airspace in a roof is one with continuous cover, such as metal, and no specific provision for ventilation.

Linear interpolation may be used to calculate the R-Value of an airspace of intermediate thickness.

R-Values are calculated using AS/NZS 4859.2 based on the following:

summer temperatures of 24°C internally and 36°C externally for heat transfer down; and

winter temperatures of 18°C internally and 12°C externally for heat transfer up; and

emittances are normal emittances of bounding surfaces in accordance with AS 4200.1.

Table for S36C2 Construction Deemed-to-Satisfy

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S36C2l.