Table S36C2l Typical R-Values for non-ventilated roof spaces with a reflective surface: Flat, skillion or pitched roof (≤5°) with horizontal ceiling, roof space not more than 300 mm thick
Specification 36 Material properties
| Emittance of airspace bounding surfaces | Thickness of roof space | Direction of heat flow | R-Value of reflective airspace |
|---|---|---|---|
| Surface 1 emittance 0.9, Surface 2 emittance 0.05 | ≤ 300 mm | Up | 0.43 |
| Surface 1 emittance 0.9, Surface 2 emittance 0.05 | 20 mm | Down | 0.60 |
| Surface 1 emittance 0.9, Surface 2 emittance 0.05 | 60 mm | Down | 1.16 |
| Surface 1 emittance 0.9, Surface 2 emittance 0.05 | 100 mm to ≤ 300 mm | Down | 1.30 |
Table Notes
A non-ventilated airspace in a roof is one with continuous cover, such as metal, and no specific provision for ventilation.
Linear interpolation may be used to calculate the R-Value of an airspace of intermediate thickness.
R-Values are calculated using AS/NZS 4859.2 based on the following:
summer temperatures of 24°C internally and 36°C externally for heat transfer down; and
winter temperatures of 18°C internally and 12°C externally for heat transfer up; and
emittances are normal emittances of bounding surfaces in accordance with AS 4200.1.
Table for S36C2 Construction Deemed-to-Satisfy
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S36C2l.