Table · NCC 2025 Volume One

Table S36C2k Typical R-Values for roof spaces with a reflective surface: Roof space > 300 mm thick or pitched roof with a horizontal ceiling

Specification 36 Material properties

Open Table S36C2k on NCC Online ↗
Direction of heat flowR-Value of reflective airspace
Ventilated roof spaceNon-ventilated roof space
Up0.340.56
Down1.361.09

Table Notes

A non-ventilated airspace in a roof is one with continuous cover, such as metal or sarked tiles, and no specific provision for ventilation.

A reflective surface is a surface with normal emittance of 0.05 or less, in accordance with AS 4200.1.

Table for S36C2 Construction Deemed-to-Satisfy

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S36C2k.

Defined terms used